Troubleshooting Using Indicators
Section 9-1
Configuring a Network with 33 Nodes or More
Problem
Status
Cause and remedy
The node is not 
present in the net-
work. 
(ERC indicator: ON
RUN indicator: OFF
INS indicator: OFF)
The ERC indicator is 
ON in the CS1W-
CLK21-V1 or CJ1W-
CLK21-V1, and a 
node address higher 
than 32 is set.
The Wired Network 62 Node Enable Bit 
in the DM Parameters Area is turned 
OFF. Turn ON the Wired Network 62 
Node Enable Bit and then turn the 
power supply OFF and ON again.
The ERC indicator is 
ON in the C200HW-
CLK21, CQM1H-
CLK21, CVM1-
CLK21, CS1W-
CLK21, or CJ1W-
CLK21, and a node 
address higher than 
32 is set.
The Units that can be used to configure 
a network that uses a node address 
higher than 32 are the CS1W-CLK21-
V1 and CJ1W-CLK21-V1 only. Either 
configure the network using compatible 
Units and Boards, or split the network 
into two separate networks.
The node is not 
present in the net-
work 
(ERC indicator: OFF
RUN indicator: ON
INS indicator: OFF)
The INS indicator is 
ON for some nodes 
in the same net-
work. Those nodes 
are C200HW-
CLK21, CQM1H-
CLK21, CVM1-
CLK21, CS1W-
CLK21, or CJ1W-
CLK21.
The INS indicator is 
ON for some nodes 
in the same net-
work. Those nodes 
are CS1W-CLK21-
V1 or CJ1W-CLK-
V1.
The Wired Network 62 Node Enable Bit 
in the DM Parameters Area of the poll-
ing node (CS1W-CLK21-V1 or CJ1W-
CLK-V1 with INS indicator ON) is OFF. 
Turn ON the Wired Network 62 Node 
Enable Bit, then turn the power supply 
OFF and ON again.
The maximum number of nodes set in 
the network parameters is less than the 
number of nodes present in the net-
work.
Use CX-Net or the Controller Link Sup-
port Software to read the network 
parameters, and check the maximum 
number of nodes setting. Set the maxi-
mum number of nodes to a number that 
is the same or larger than the number 
of nodes in the network.
The maximum num-
ber of nodes in the 
network is set to 32.
The polling node is a 
C200HW-CLK21, 
CQM1H-CLK21, 
CVM1-CLK21, 
CS1W-CLK21, or 
CJ1W-CLK21. 
The Units that can be used to configure 
a network that uses a node address 
higher than 32 are the CS1W-CLK21-
V1 and CJ1W-CLK21-V1 only. Either 
configure the network using compatible 
Units and Boards, or split the network 
into two separate networks.
The polling node is a 
CS1W-CLK21-V1 or 
CJ1W-CLK-V1.
The Wired Network 62 Node Enable Bit 
in the DM Parameters Area of the poll-
ing node (CS1W-CLK21-V1 or CJ1W-
CLK-V1 with INS indicator ON) is OFF. 
Turn ON the Wired Network 62 Node 
Enable Bit, then turn the power supply 
OFF and ON again.