Omron CS1W-RPT01 Manuale Utente

Pagina di 401
282
Troubleshooting Using Indicators
Section 9-1
The data link status 
is showing statuses 
of 32 nodes only.
The data link status 
storage area is set to 
default settings, and 
the data link status 
storage format speci-
fication in the DM 
Parameters Area is 
set to the 8-bit for-
mat. 
The default area for storing data link 
status is the Special I/O Unit Area. The 
data for only node addresses 1 to 32 is 
reflected when the data link status stor-
age format specification is set to 8 bits. 
The polling node is a 
C200HW-CLK21, 
CQM1H-CLK21, 
CVM1-CLK21, 
CS1W-CLK21, or 
CJ1W-CLK21. 
The Units that can be used to configure 
a network of a network that uses a 
node address higher than 32 are the 
CS1W-CLK21-V1 and CJ1W-CLK21-
V1 only. Either configure the network 
using compatible Units and Boards, or 
split the network into two separate net-
works.
The polling node is a 
CS1W-CLK21-V1 or 
CJ1W-CLK-V1.
The Wired Network 62 Node Enable Bit 
in the DM Parameters Area of the poll-
ing node (CS1W-CLK21-V1 or CJ1W-
CLK-V1 with INS indicator ON) is OFF. 
Turn ON the Wired Network 62 Node 
Enable Bit, then turn the power supply 
OFF and ON again.
Error occurs when 
transferring data link 
tables.
The data link table 
being transferred is 
for a C200HW-
CLK21, CQM1H-
CLK21, CVM1-
CLK21, CS1W-
CLK21, or CJ1W-
CLK21. 
The Units that can be used to configure 
a network of a network that uses a 
node address higher than 32 are the 
CS1W-CLK21-V1 and CJ1W-CLK21-
V1 only. Either configure the network 
using compatible Units and Boards, or 
split the network into two separate net-
works.
The data link status 
is showing statuses 
of 32 nodes only.
The polling node is a 
C200HW-CLK21, 
CQM1H-CLK21, 
CVM1-CLK21, 
CS1W-CLK21, or 
CJ1W-CLK21. 
The polling node is a 
CS1W-CLK21-V1 or 
CJ1W-CLK-V1.
The Wired Network 62 Node Enable Bit 
in the DM Parameters Area of the poll-
ing node (CS1W-CLK21-V1 or CJ1W-
CLK-V1 with INS indicator ON) is OFF. 
Turn ON the Wired Network 62 Node 
Enable Bit, then turn the power supply 
OFF and ON again.
Problem
Status
Cause and remedy