Omron CS1W-RPT01 Manuale Utente

Pagina di 401
302
Status Area and Troubleshooting
Section 9-2
Data link participation is 0: 
OFF
The relevant node is not 
part of data links.
Enter the relevant node in 
data links. If an error 
occurs, refer to page 280 
Node Cannot Participate in 
Data Link
 and troubleshoot 
accordingly.
There are no active data 
links in the Network.
Activate the data links.
Offset error is 1: ON
The offset is greater than 
the number of send words 
at the relevant node.
Check the number of send 
words at the relevant node, 
the number of receive 
words at the local node 
and the offset, then reset 
the data link table correctly.
Receive area insufficient 
(short) is 1: ON
The send area at the rele-
vant node is larger than the 
receive area and some 
data cannot be received.
When the intention is not to 
receive all data, use as is 
(data that cannot be 
received will be read and 
discarded.) 
When it differs from the 
intended data link, check 
the number of send words 
at the relevant node, the 
number of receive words at 
the local node and the off-
set, then reset the data link 
table correctly.
Receive area remaining is 
1: ON
The send area at the rele-
vant node is smaller than 
the receive area and some 
of the area will be unused.
When the intention is to 
leave some space in the 
receive area, use as is (the 
remaining receive area will 
be cleared to 0.)
When it differs from the 
intended data link, check 
the number of send words 
at the relevant node, the 
number of receive words at 
the local node and the off-
set, then reset the data link 
table correctly.
Bit status
Probable cause