Status Area and Troubleshooting
Section 9-2
Other Status
Bit status
Probable cause
Probable remedy
Duplicate Operating Lev-
els/Refresh Error: 
Operating level 0: AR0011 
Operating level 1: AR0010 
One of the above flags is 1: 
ON
The same operating level is 
set twice within the same 
PLC.
If two units are required, 
set them to different oper-
ating levels.
A refresh error has 
occurred between the PLC 
and the Unit.
Secure the Controller Link 
Unit firmly.
For C200HX/HG/HE PLCs, 
tighten the screws on the 
Bus Connection Unit.
If the error occurs even 
when the Unit is mounted 
on another PLC, replace 
the Controller Link Unit.
Routing Table Error/Unit 
Restart: 
Operating level 0: AR0113 
Operating level 1: AR0112
One of the above flags is 1: 
ON
The routing table data 
within the DM Area is dam-
aged.
Refer to 7-4 Setting Rout-
ing Tables
 and reset cor-
rectly. If the error occurs 
again, replace the Control-
ler Link Unit.
There is an error in the 
routing table setting or a 
Routing Table Enable Bit 
(software switch) setting 
error.
When using routing tables 
refer to 7-4 Setting Routing 
Tables
 an
d reset them cor-
rectly.
When no routing tables are 
being used, turn OFF the 
Routing Table Enable Flag.
Communications controller 
hardware error:
Operating level 0: AR1114 
Operating level 1: AR1514 
One of the above flags is 1: 
ON
The Controller Link Unit is 
faulty.
Replace the Controller Link 
Unit.
EEPROM error:
Operating level 0: AR1115 
Operating level 1: AR1515 
One of the above flags is 1: 
ON
An error occurred when 
writing data to EEPROM.
Remake and set the data 
link table and the network 
parameters. If the error 
occurs again, replace the 
Controller Link Unit.
The EEPROM data link 
tables or the network 
parameters are damaged.
There is an error in the 
data link or network param-
eter settings.
Inconsistent network 
parameters:
Operating level 0: AR2407 
Operating level 1: AR2406
One of the above flags is 1: 
ON
Indicates that the network 
parameters in the 
EEPROM of the Controller 
Link Unit differ from those 
in the Network.
Check the network param-
eters on the Network, 
using the Controller Link 
Support Software, and 
reset the necessary 
parameters.