Omron CS1W-RPT01 Manuale Utente

Pagina di 401
305
Status Area and Troubleshooting
Section 9-2
Data Link Status: CIO 1500 + 25 
×
 (Unit No.) + 7 to + 22
When the first data link status word is set to the default (0000) for either the
manually set data link tables or automatically set data link tables (In the first
data link status word parameter), the data link status is stored in the above
area (CIO 1500 + 25 
× 
(Unit No.) (+ 7 to +22)).
When a different area has been set for the first data link status word, the sta-
tus is stored in the specified area. The status storage format is the same as
the one shown in the above diagram.
Note Refer to 5-4 Checking Data Link Status for details on status flags.
Bit Status and Error Processing
Data Link Status
Node   2
Node   4
Node   6
Node   8
Node   10
Node   12
Node   14
Node   16
Node   18
Node   20
Node   22
Node   24
Node   26
Node   28
Node   30
Node   32
PLC status
0: Inactive (user program not running)
1: Active (user program running)
Communications error (data link reception)
0: Normal
1: Error
PLC's CPU Unit error
0: Normal
1: Error
Data link participation
0: Not in data link or data link inactive
1: In data link
Offset error 
0: Normal
1: Error
Error: Offset exceeds 
number of send words.
Insufficient (short) receive area
0: Sufficient
1: Insufficient
Insufficient: Receive 
area is smaller than 
send area. Excess data 
is truncated; other data 
is received.
Remaining receive area
0: Not remaining
1: Remaining
Remaining: Receive 
area is larger than send 
area. Data is received 
and remaining words 
are cleared.
Node   1
Node   3
Node   5
Node   7
Node   9
Node   11
Node   13
Node   15
Node   17
Node   19
Node   21
Node   23
Node   25
Node   27
Node   29
Node   31
+7
+8
+9
+10
+11
+12
+13
+14
+15
+16
+17
+18
+19
+20
+21
+22
Bit status
Probable cause
Probable remedy
PLC’s CPU Unit error is 1: 
ON
A fatal PLC error, non-fatal 
PLC error, or a watchdog 
timer error has occurred.
Refer to the PLC’s opera-
tion manual and correct 
the error. If the error occurs 
again, replace the PLC.
The Unit is mounted to a 
non-compatible PLC.
Refer to 1-2-4 Controller 
Link Unit Models and PLCs
 
and mount onto the correct 
PLC.