Status Area and Troubleshooting
Section 9-2
Other Status
Receive area insufficient 
(short) is 1: ON
The send area at the rele-
vant node is larger than the 
receive area and some 
data cannot be received.
When the intention is not to 
receive all data, use as is 
(data that cannot be 
received will be read and 
discarded.) 
When it differs from the 
intended data link, check 
the number of send words 
at the relevant node, the 
number of receive words at 
the local node and the off-
set, then reset the data link 
table correctly.
Receive area remaining is 
1: ON
The send area at the rele-
vant node is smaller than 
the receive area and some 
of the area will be unused.
When the intention is to 
leave some space in the 
receive area, use as is (the 
surplus receive area will be 
cleared to 0.)
When it differs from the 
intended data link, check 
the number of send words 
at the relevant node, the 
number of receive words at 
the local node and the off-
set, then reset the data link 
table correctly.
Bit status
Probable cause
Probable remedy
Bit status
Probable cause
Probable remedy
Error log exists (IR 19015) 
is 1: ON
Error information on the 
Controller Link Unit (an 
error log) has been 
recorded.
Using the Controller Link 
Support Software or an 
FINS command, read the 
cause of the current error. 
Alternatively, use past error 
log records to troubleshoot 
the problem.
Communications controller 
send error (IR 19011) is 1: 
ON
The Controller Link Unit is 
faulty.
Replace the Controller Link 
Unit.
Inconsistent network 
parameters (IR 19010) is 1: 
ON
Indicates that the network 
parameters recorded in the 
CPU Unit’s EEPROM differ 
from the values of the Net-
work in use.
Check the network param-
eters on the Network in 
use using the Controller 
Link Support Software, and 
reset necessary parame-
ters.
Node address duplicate 
setting error (IR 19009) is 
1: ON
The same node address 
has been used more than 
once.
Reset so that each node 
address is used only once 
within the same Network.
EEPROM error (IR 19007) 
is 1: ON
An error has occurred 
while writing data to the 
CPU Unit’s EEPROM.
Check the status of bits 
IR 19000 to IR 19002 and 
correct any problems 
found. If the error occurs 
again, replace the CPU 
Unit.