Status Area and Troubleshooting
Section 9-2
Terminating Resistance Status: IR 95
Routing table error 
(IR 19002) is 1: ON
The routing table data 
within the CPU Unit’s 
EEPROM is damaged.
Refer to 7-4 Setting Rout-
ing Tables
 a
nd reset the 
routing tables correctly. If 
the error occurs again, 
replace the Controller Link 
Unit.
There is an error in the 
routing table setting.
When using a routing 
table, refer to 7-4 Setting 
Routing Tabless
 and reset 
the routing tables correctly.
If no routing tables are 
being used, delete the 
tables.
Data link table error 
(IR 19001) is 1: ON
The data link table data in 
the EEPROM of the CPU 
Unit is damaged.
Refer to 5-3 Starting and 
Stopping Data Links
 and 
reset the data link tables 
correctly. If the error occurs 
again, replace the CPU 
Unit.
There is an error in the 
data link table settings.
When using manually set 
data links, refer to 5-3 
Starting and Stopping Data 
Links 
and remake and set 
the data link tables cor-
rectly. When manually set 
data links are not being 
used, delete the data link 
tables.
Network parameter error 
(IR 19000) is 1: ON
The CPU Unit’s EEPROM 
data link tables or the net-
work parameters are dam-
aged.
Refer to 8-1-3 Network 
Parameters
 an
d reset the 
data correctly. If the error 
occurs again, replace the 
CPU Unit.
Either set the EEPROM 
Clear Bit in the DM Param-
eter Area to ON, or use the 
Initialize network parame-
ters operation on the Main-
tenance Menu of the 
Controller Link Support 
Software to initialize the 
network parameters and 
then cycle the power sup-
ply.
There is an error in the net-
work parameter settings, or 
node address of the local 
node is larger then the 
maximum address set 
within the network parame-
ters.
Refer to 8-1-3 Network 
Parameters
 an
d reset the 
network parameters or the 
node address.
Bit status
Probable cause
Probable remedy
Terminating resistance status: 0: OFF
            1: ON