Delta Electronics VFD007S23A Manuale Utente
Chapter 5 Parameters|VFD-S Series
5-4
Revision August 2006, SE08, SW V2.61
Pr. Explanation
Settings
Factory
Setting
NOTE
2-00
Source of Master Frequency
Command
Command
d4: Master Frequency operated by
RS-485 serial communication
interface and record frequency
of power loss. (record the
frequency of power loss and it
can do analog overlap plus)
interface and record frequency
of power loss. (record the
frequency of power loss and it
can do analog overlap plus)
d5: Master Frequency operated by
RS-485 serial communication
interface and won’t record
frequency before power loss.
(won’t record the frequency of
power loss and it can do analog
overlap plus)
interface and won’t record
frequency before power loss.
(won’t record the frequency of
power loss and it can do analog
overlap plus)
d0
2-01
Source of Operation
Command
Command
d0: Digital Keypad
d1: External terminals. Keypad
d1: External terminals. Keypad
STOP/RESET enabled.
d2: External terminals. Keypad
STOP/RESET disabled.
d3: RS-485 serial communication
(RJ-11) .Keypad STOP/RESET
enabled.
enabled.
d4: RS-485 serial communication
(RJ-11). Keypad STOP/RESET
disabled.
disabled.
d0
2-02 Stop
Method
d0: STOP: ramp to stop; E.F.: coast
to stop
d1: STOP: coast to stop; E.F.: coast
to stop
d0
2-03
PWM Carrier Frequency Selections
d3: 3KHz
d4: 4KHz
d5: 5KHz
d6: 6KHz
d7: 7KHz
d8: 8KHz
d9: 9KHz
d10: 10KHz
d4: 4KHz
d5: 5KHz
d6: 6KHz
d7: 7KHz
d8: 8KHz
d9: 9KHz
d10: 10KHz
d10
2-04
Motor Direction Control
d0: Enable forward/reverse
operation
d1: Disable reverse operation
d0
2-05
Loss of ACI Signal
d0: Decelerate to 0 Hz
d1: Coast to stop and display “EF”
d2: Continue operation by last
d1: Coast to stop and display “EF”
d2: Continue operation by last
frequency command
d0
2-06
Analog Auxiliary Frequency Operation
d0: Disable
d1: Enable + AVI
d2: Enable + ACI
d1: Enable + AVI
d2: Enable + ACI
d0
Group 3 Output Function Parameters