Chapter 7      Maintaining the Router
Removing and Replacing Blower Modules
7-28
Cisco 12016, Cisco 12416, and Cisco 12816 Router Installation and Configuration Guide
OL-11495-01
Troubleshooting the Blower Installation
Use the following procedure to troubleshoot a blower module if it is not operating 
properly after installation.
Step 1
Be sure the router is powered on and that all power cords are connected properly.
Step 2
Loosen the captive screws and reseat the blower module to the chassis.
  •
Retighten the captive screws to ensure the blower module is properly seated 
to the backplane connector.
Step 3
Check the blower module status indicators:
  •
OK (green)—Indicates that the blower module is operating normally. This 
indicator should light as soon as the blower module is installed and receives 
power from the backplane connector.
  –
If this indicator remains on, and the blower module fans fail to operate 
after several attempts to reseat the blower module, replace it with a spare.
  –
If the spare blower module also fails, power off the router and contact a 
Cisco service representative for assistance.
  •
FAIL (red)—During normal operation, this indicator remains off. If this 
indicator is on, the system has detected a fan failure or other fault in the 
blower module.
  –
If this indicator remains on, and the blower module fans fail to operate 
after several attempts to reseat the blower module, replace it with a spare.
  –
If the spare blower module also fails, power off the router and contact a 
Cisco service representative for assistance.