Black Box CRDX-A-FS-12KW Manuale Utente

Pagina di 132
724-746-5500   |   blackbox.com 
724-746-5500   |   blackbox.com 
Page 103
Chapter 4: E2 Controller
4.8 Troubleshooting the Control I/O Module Signal LEDs
The E2 control I/O module includes three signal LEDs (red, yellow, and green) that provide information on the operation of the 
control module and status of the connection to the pLAN. These signal LEDs are positioned adjacent to the yellow “Power On” 
LED (see Figure 4-2). The signal LEDs may be used for diagnostic purposes if a problem arises with the controller.
 
Key:   
  LED off  
 
 
   LED on  
 
 
   LED flashing
Table 4-26. I/O control module signal LEDs.
Red LED
Yellow LED
Green LED
Description
Application with error or no pLAN table.
Application with error or no pLAN table. Controller connected to ONLY one terminal.
Application with correct pLAN table.
Correct operation in pLAN.
Awaiting communication with WinLoad (factory configuration software). Check address.
  /
/
(LED flashing alternately) Communication with WinLoad not valid. No power supply or wrong 
driver.
Communicating with WinLoad (in low-level operation).
Communication with WinLoad on hold.
WinLoad not suitable or incorrect software protection password.
Communicating with WinLoad (in normal operation).
Controller supervisor protocol (slave) active on serial 0.