Chapter 4: E2 Controller
4.9.1 Signed Values for HTTP, SNMP/Modbus Holding Registers/Analog Values for BACnet
Table 4-28. Signed Values for HTTP, SNMP/Modbus Holding Registers/Analog Values for BACnet.
BMS 
Address
Modbus 
Address
BACnet 
Address
Description 
Default 
Read/Write
1
002
1
Temperature setpoint
72.0
R/W
2
003
2
Humidity setpoint
45.0
R/Ws
3
004
3
Average supply temperature display value
0.0
R
4
005
4
Return humidity sensor current value
0.0
R
5
006
5
Dewpoint of return temperature and humidity
0.0
R
6
007
6
Dewpoint of remote temperature and humidity
0.0
R
7
008
7
Middle fan speed
0.0
R
8
009
8
Upper fan speed
0.0
R
9
010
9
Lower fan speed
0.0
R
10
011
10
Middle fan manual speed
0.0
R/W
11
012
11
Upper fan manual speed
0.0
R/W
12
013
12
Lower fan manual speed
0.0
R/W
13
014
13
Static pressure sensor current value
0.0
R
14
015
14
C1 discharge pressure sensor current value
0.0
R
15
016
15
C1 suction pressure sensor current value
0.0
R
16
017
16
C1 suction temperature sensor current value
0.0
R
17
018
17
Return temperature display value
0.0
R
18
019
18
Remote temperature display value
0.0
R
19
020
19
Entering water temperature display value
0.0
R
20
021
20
Leaving water temperature display value
0.0
R
100
101
100
High air temperature alarm limit
80.0
R/W
101
102
101
Low temperature alarm limit
60.0
R/W
102
103
102
High humidity alarm limit
70.0
R/W
103
104
103
Low humidity alarm limit
30.0
R/W
104
105
104
High water temperature limit
60.0
R/W
105
106
105
Low water temperature alarm limit
40.0
R/W