4.9.4 Alarm Packed Bit Variables
Table 4-32. Alarm-Packed Bit Variables.
Bit
Alarms 1
Alarms 2
Alarms 3
0
Emergency shutdown
Middle fan alarm
Reserved
1
Remote shutdown
Upper fan alarm
Reserved
2
Customer Alarm 1
Lower fan alarm
Reserved
3
Airflow
High temperature
Reserved
4
Filter
Low temperature
Reserved
5
Fire/Smoke
High humidity
Reserved
6
Water detection
Low humidity
Reserved
7
Condensate pan
High water temp CW1
Reserved
8
Moisture
Low water temp CW1
Reserved
9
Circuit 1 low pressure
Customer Alarm 2
Reserved
10
Circuit 1 high pressure
Customer Alarm 3
Reserved
11
Pump
Flow alarm (temp sensors)
Reserved
12
Dual power input A
Flow alarm (flow switch) 
Reserved
13
Dual power input B
Reserved
Reserved
14
Humidifier
Reserved
Reserved
15
Loss of power
Reserved