Chapter 4: E2 Controller
4.9.2 Unsigned Values for HTTP, SNMP/Modbus Holding Registers/Analog Values for BACnet
Table 4-29. Unsigned Values for HTTP, SNMP/Modbus Holding Registers/Analog Values for BACnet.
BMS 
Address
Modbus 
Address
BACnet 
Address
Description 
Default 
Read/Write
1
130
1001
Cooling analog output
0
R
2
131
1002
Middle fan Speed analog output
0
R
3
132
1003
Upper fan analog control value
0
R
4
133
1004
Lower Fan analog control value
0
R
5
134
1005
Packed bit for BMS - alarms
0
R
6
135
1006
Packed bit for BMS - alarms
0
R
7
136
1007
Packed bit for BMS - alarms
0
R
8
137
1008
Packed bit for BMS - sensor fails
0
R
9
138
1009
Packed bit for BMS - sensor fails
0
R
10
139
1010
Packed bit for BMS - digital inputs
0
R
11
140
1011
Packed bit for BMS - digital inputs
0
R
12
141
1012
Packed bit for BMS - digital outputs
0
R
13
142
1013
Packed bit for BMS - digital outputs
0
R
15
144
1015
Prop humidifier control output
0
R
16
145
1016
Head pressure control output
0
R
100
229
1100
BMS keep alive parameter
0
R/W
101
230
1101
BMS low fan speed for CW units
0
R/W
102
231
1102
BMS run fan speed for CW units
0
R/W
103
232
1103
BMS dehumidifier fan speed for CW units
0
R/W
104
233
1104
Fan link control (0 to 4) See 4.9.2.1
0
R/W
105
234
1105
Control mode of dewpoint, hybrid, standard
0
R/W
106
235
1106
Temperature control sensor selection
0
R/W
107
236
1107
Humidity control sensor selection
0
R/W
108
237
1108
Type of unit (valid numbers 0 to 6) See 4.9.2.1
0
R/W
110
239
1110
Lower fan speed control (0 to 2) See 4.9.2.1 
0
R/W
111
240
1111
Middle fan speed control (0 to 2) See 4.9.2.1
0
R/W
112
241
1112
Upper fan speed control (0 to 2) See 4.9.2.1
0
R/W
123
252
1123
Current day
0
R/W
124
253
1124
Current month
1
R/W
125
254
1125
Current year
1
R/W
126
255
1126
Current hour
0
R/W
127
256
1127
Current minute
0
R/W