American Power Conversion SUOL2000UXI Manuale Utente

Pagina di 16
 
990-1137, 3/02 
2. C
ONNECT THE 
E
XTERNAL 
B
ATTERIES
 
 
 
 
 
 
   
3. C
ONNECT THE EQUIPMENT TO THE 
UPS 
AND 
C
ONNECT THE 
UPS 
TO THE 
AC P
OWER
 
S
UPPLY
 
1.  On the back panel, plug the female end of the power cord into the receptacle.  Then plug the 
male end into a two-pole, three-wire, grounding receptacle. Avoid using extension cords and 
adapter plugs. 
2.  Connect the equipment to the UPS using the power cords provided with the equipment. 
3.  Turn on all connected equipment. To use the UPS as a master ON/OFF switch, be sure all con-
nected equipment is switched on. The equipment will not be powered until the UPS is turned on. 
4. T
URN ON THE 
UPS 
Make sure the battery is connected before turning on the UPS!  Press the 
 button on the front 
panel to power up your UPS.  This will power up connected equipment if that equipment is turned 
on.  
 
The UPS charges the batteries when it is connected to utility power. Do not expect full 
run time during this initial charge period. Time depends on number and type of batter-
ies. 
The unit performs a self-test automatically when turned on and every two weeks thereafter (by de-
fault). Refer to the User Configurable Items section of this manual, below, for details on changing 
the default interval. 
To turn on the UPS when no utility power is present, see the Cold Start function in the Operations 
section of this manual. 
 
Battery  
Connector 
On Rear  
Panel  
Step A 
Step B
1. Refer 
to 
www.apc.com/support
 for the Smart-
UPS On-Line Battery Pack User Manual (990-
1083). 
2.  If using a non-APC battery pack, a 48V battery 
string should be wired to the UPS using the en-
closed battery cable assembly. 
Batteries must be Sealed Lead-Acid type. 
Each string of four 12V batteries must be 
provided with an 80-100 amp fuse or fuse-
able link to protect in the event of a short 
circuit.
48 Volt System 
80-100 
Amp 
Fuse