American Power Conversion InfraStruXureTM System Manuale Utente

Pagina di 100
Appendix A : System Operation
72
InfraStruXure System—Installation and Start-Up
c. Select UPS Into Bypass on the Control menu, and 
press the 
E
NTER
 key.
Control Menu
d. Confirm the selection on the next screen: select Yes, 
UPS into Bypass, and press the 
E
NTER
 key. 
Confirmation Screen
Note
The H2 LED above the Q2 circuit breaker illuminates, indicating that it is 
safe to operate the Q2 circuit breaker.
7. Close (turn ON) the Q2 circuit breaker on the PDU.
Note
The H3 LED above the Q3 circuit breaker illuminates, indicating that it is safe to 
operate the Q3 circuit breaker
8. Open (turn OFF) the Q3 circuit breaker on the PDU.
The UPS automatically comes out of Static Bypass 
operation.
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load On
Confirm
Yes, UPS into Bypass
No, Abort