American Power Conversion AIS 5000 Manuale Utente

Pagina di 82
External Connection - 30kVA 400V UPS
34
AIS 5000 400V Installation Manual
990-2440
Emergency Power Off (EPO)
Yes
Physical Values
Dimensions (H × W × D)
Unit 
1,800 × 825 × 810 mm
Shipping
2,080 × 1,016 × 1,016 mm
Weight
Unit 750 
kg
Shipping
790 kg
Max. Power Cable size [mm]
50
Recommended Cable sizes
Ext. Input Cable [mm]
10
Ground Cable [mm]
10
Ext. Output Cable [mm]
10
Ext. Battery Cable [mm]
50
Ext. Alarm Cable Max. [mm]
1.5
Recommended Conduit sizes
Input
1.25”
Output
3/4”
Battery
1.25”
Alarm
1/2”
Environmental Values
Temperature
Operating
0
o
 - 40
o
 C
Storage
-40
o
 - 70
o
 C
Elevation
Operating
0 - 1,000 m
Storage
0 - 5,000 m
Humidity
Max. 95% non-conditioned
Protection Class
IP30 (IP32 optional)
Transient Attenuation
Differential mode 60 to 80 dB, Common mode 120 dB
Audible Noise at 3.28 feet (1 m)
60-70 dB, depending on type
Compliance
Approvals
IEC 62040/EN 50091 Class A, VFI-SS-112
Communication and Management