American Power Conversion AIS 5000 Manuale Utente

Pagina di 82
36
AIS 5000 400V Installation Manual
990-2440
40kVA 400V UPS
IS40KH
Performance - Linear Load
DC to AC Efficiency [%]
90.8
AC to AC Efficiency [%]
87.0
Heat Dissipation [BTU/h] [W]
16,333/4,782
Electrical Input
Mains
Voltage
400 V 3 Wire + G
P Nom.
36.9 kW
I Nom. 
(Nominal input current based on nominal mains 
voltage and batteries fully charged at 100% ohmic 
load)
61.93 A
I Max.
(Maximum input current based on full battery 
recharge and nominal mains voltage at 100% ohmic 
load)
77.8 A
Over-Current protection [A]
(Based on continuous full load)
80 A
Input Voltage Range
+ 10%, -15% programmable
Input Frequency
50 Hz + 6% programmable
Current Distortion
< 12%
Power Factor
0.8 - 0.9
Bypass
Voltage
400 V 3 Wire + N + G
I Nom
48.1 A
Over-Current protection [A]
(Based on continuous full load)
60 A
Bypass Voltage Range
+ 10% programmable
Electrical Output
Voltage
400 V 3 Wire + N + G
Nominal current 
(The output current is based on the nominal apparent 
power of the UPS)
57.7 A
Frequency Range
50Hz (adjustable 0.25, 0.50, 1-8%)