Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
146
Output
Source
40050
1
1 = Other
2 = None
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
Frequency
40051
1
10
Units: Hz
Number Lines
40052
1
Voltage L1
40053
1
Units: V
Voltage L2
40054
1
Units: V
Voltage L3
40055
1
Units: V
Current L1
40056
1
10
Units: A
Current L2
40057
1
10
Units: A
Current L3
40058
1
10
Units: A
Real Power L1
40059
1
10
Units: kW
Real Power L2
40060
1
10
Units: kW
Real Power L3
40061
1
10
Units: kW
Percent Load L1
40062
1
Units: %
Percent Load L2
40063
1
Units: %
Percent Load L3
40064
1
Units: %
Bypass
Line Bads
40070
1
Frequency
40071
1
10
Units: Hz
Number Lines
40072
1
Voltage L1
40073
1
Units: V
Voltage L2
40074
1
Units: V
Voltage L3
40075
1
Units: V
Current L1
40076
1
10
Units: A
Current L2
40077
1
10
Units: A
Current L3
40078
1
10
Units: A
Alarms
Alarms Present
40087
1
Bit 0
On Battery
40087
1
Bit 2
Low Battery
40087
1
Bit 3
Depleted Battery
40087
1
Bit 4
Temperature Bad
40087
1
Bit 5
Input Bad
40087
1
Bit 6
Output Overload
40088
1
Bit 0
On Bypass
40088
1
Bit 1
Bypass Bad
40088
1
Bit 2
Charger Failed
40088
1
Bit 5
Fan Failure
40089
1
Bit 0
General Fault
40089
1
Bit 2
Table 54
Liebert NX 225-600kVA UPS - Input and Holding
3
 (continued)
Data Description
Input
Holding
Register
# of
Reg
Scale
Notes/Units