Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
148
Table 55
Liebert NXL
 - 60Hz, UL version (Model 40) - Status and Coil
Data Label
Status
Coil
# of Bits
Notes
NXL Type
Battery Self Test
10082
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Low Shutdown
10092
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Shutdown - REPO
10093
1
Active on Alarm
N+1, 1+N, 1+1, SMS
UPS Output on Bypass
10129
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Output Load on Maint. Bypass
10132
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Main Battery Disconnect Open
10136
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Bypass - Excess Auto Retransfers
10147
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Battery Low
10152
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Shutdown - EPO
10157
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Output Off
10158
1
Active on Alarm
Deprecated
Battery Over Temperature
10172
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Inlet Air Over Temperature
10173
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Input Current Imbalance
10185
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Input Phs Rotation Error
10191
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Rectifier Failure
10259
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Inverter Failure
10263
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Main Controller Fault
10293
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Bypass Not Available
10321
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Overload Phase A
10322
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Overload Phase B
10323
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Overload Phase C
10324
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Auto Retransfer Failed
10325
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Static Switch Unavailable
10326
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Static Switch Overload
10327
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Excessive Pulse Parallel
10328
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Auto Transfer Failed
10329
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Frequency Error
10330
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass - Manual Rexfr Inhibited
10331
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass - Manual Xfr Inhibited
10332
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Static Switch Off Extrnl
10333
1
Active on Alarm
CE only
Battery Charging Reduced-Extrnl
10334
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Capacity Low
10335
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Discharging
10336
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Temperature Imbalance
10337
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Temperature Sensor Fault
10338
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Charging Inhibited
10339
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 1 Open
10340
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 2 Open
10341
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 3 Open
10342
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 4 Open
10343
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 5 Open
10344
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 6 Open
10345
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 7 Open
10346
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 8 Open
10347
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery - External Monitor 1
10348
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery - External Monitor 2
10349
1
Active on Alarm
N+1, 1+N, 1+1, SMS