Emerson BACNET IP Manuale Utente
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
150
Controls Reset Required
10397
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Battery Test Failed
10398
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Auto Restart Inhibited - Ext
10399
—
1
Active on Alarm
SCC, SMS
Battery Test Inhibited
10400
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Equalize
10401
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Backfeed Breaker Open
10402
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
On Generator
10403
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Power Supply Failure
10404
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Battery Ground Fault
10405
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Charging Error
10406
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Input Power Problem
10407
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Input Current Limit
10408
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Internal Communications Failure
10409
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
System Controller Error
10410
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Output
Output Of/Uf
Output Of/Uf
10510
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
MultiModule
Parallel Comm Warning
Parallel Comm Warning
10521
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1
System Comm Fail
10522
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1
Loss of Redundancy
10523
—
1
Active on Alarm
SCC, 1+N, 1+1
BPSS Startup Inhibit
10524
—
1
Active on Alarm
Deprecated
MMS Transfer Inhibit
10525
—
1
Active on Alarm
SCC, 1+N, 1+1
MMS Retransfer Inhibit
10526
—
1
Active on Alarm
SCC, 1+N, 1+1
MMS Loss of Sync Pulse
10527
—
1
Active on Alarm
Deprecated
MMS Overload
10528
—
1
Active on Alarm
SCC
MMS On Battery
10529
—
1
Active on Alarm
SCC, 1+N, 1+1
MMS Low Battery Warning
10530
—
1
Active on Alarm
SCC, 1+N, 1+1
MMS Module Alarm Active
10531
—
1
Active on Alarm
SCC
MMS Sharing Calib Active
10532
—
1
Active on Alarm
SCC
Intelligent Paralleling
Module In Standby - Intelligent Paralleling
Module In Standby - Intelligent Paralleling
10543
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1
ECO Mode
ECO Mode Active
ECO Mode Active
10554
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
ECO Mode Suspended
10555
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Excess ECO Suspends
10556
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
System
LBS Active - Master
LBS Active - Master
10567
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
LBS Active - Slave
10568
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
EMO Shutdown
10575
—
1
Active on Alarm
SMS, 1+N, N+1, SCC
Cont Tie Active
10576
—
1
Active on Alarm
SMS, 1+N, N+1, SCC
User kWh Reset
10577
—
1
Active on Alarm
SMS, 1+N, N+1, SCC
Peak kW Reset
10578
—
1
Active on Alarm
SMS, 1+N, N+1, SCC
Environment
Outlet Air Overtemperature Limit
Outlet Air Overtemperature Limit
10580
—
1
Active on Alarm
SCC, SMS, 1+N, N+1
Service Reminder
Service Required
Service Required
10590
—
1
Active on Alarm
SMS, 1+N, N+1, SCC
Table 55
Liebert NXL
™
- 60Hz, UL version (Model 40) - Status and Coil (continued)
Data Label
Status
Coil
# of Bits
Notes
NXL Type