Emerson BACNET IP Manuale Utente
BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
280
XD System 1
Ext System Condensation Detected
Ext System Condensation Detected
Binary_Value
112
5492_1
RD
—
Ext Fan Issue
Binary_Value
113
5495_1
RD
—
Sensor Issue
Binary_Value
114
5060_1
RD
—
Ext Remote Shutdown
Binary_Value
115
5500_1
RD
—
Hot Aisle Temp Out of Range
Binary_Value
116
5505_1
RD
—
Cold Aisle Temp Out of Range
Binary_Value
117
5508_1
RD
—
XD System 2
Ext System Condensation Detected
Ext System Condensation Detected
Binary_Value
128
5492_2
RD
—
Ext Fan Issue
Binary_Value
129
5495_2
RD
—
Sensor Issue
Binary_Value
130
5060_2
RD
—
Ext Remote Shutdown
Binary_Value
131
5500_2
RD
—
Hot Aisle Temp Out of Range
Binary_Value
132
5505_2
RD
—
Cold Aisle Temp Out of Range
Binary_Value
133
5508_2
RD
—
XD System 20
Ext System Condensation Detected
Ext System Condensation Detected
Binary_Value
416
5492_20
RD
—
Ext Fan Issue
Binary_Value
417
5495_20
RD
—
Sensor Issue
Binary_Value
418
5060_20
RD
—
Ext Remote Shutdown
Binary_Value
419
5500_20
RD
—
Hot Aisle Temp Out of Range
Binary_Value
420
5505_20
RD
—
Cold Aisle Temp Out of Range
Binary_Value
421
5508_20
RD
—
System Events
Customer Input 1
Customer Input 1
Binary_Value
432
4270_1
RD
—
System Condensation Detected
Binary_Value
433
4711_1
RD
—
Shutdown - Loss Of Power
Binary_Value
434
4714_1
RD
—
Smoke Detected
Binary_Value
435
4720_1
RD
—
Water Under Floor
Binary_Value
436
4723_1
RD
—
Service Required
Binary_Value
437
4726_1
RD
—
Fan Issue
Binary_Value
438
4729_1
RD
—
Unit Communication Lost
Binary_Value
439
5419_1
RD
—
RAM Battery Issue
Binary_Value
440
5119_1
RD
—
Master Unit Communication Lost
Binary_Value
441
5120_1
RD
—
Remote Shutdown
Binary_Value
442
5512_1
RD
—
Unit Code Missing
Binary_Value
443
5418_1
RD
—
System Events - Messages
Unit On
Unit On
Binary_Value
454
5109_1_1
RD
—
Unit Off
Binary_Value
455
5110_1_1
RD
—
Unit Standby
Binary_Value
456
5111_1_1
RD
—
Unit Partial Shutdown
Binary_Value
457
5112_1_1
RD
—
Unit Shutdown
Binary_Value
458
5113_1_1
RD
—
Maintenance Due
Binary_Value
459
5116_1_1
RD
—
Maintenance Completed
Binary_Value
460
5117_1_1
RD
—
Table 92
Liebert XDP
™
, Liebert XDC
™
- Binary Data (continued)
Controller
Liebert iCOM
®
v4
Data Label
Object Type
Instance
Object
Name
Access
Notes