"Batt Group" Parameter Settings: 
 
EQ/FLT Control*: Places the system in Equalize Charge or Float Charge mode. 
 
BattTestControl*: Starts or stops a Battery Test. 
 
Reset Batt Cap*: Resets the battery capacity calculation. 
 
Clr Bad Bat Alm*: Clears a bad battery alarm. 
 
Clr LiBatt Lost*: Clears a Li-Ion battery lost alarm. 
 
ClrLiBatComFail*: Clears a Li-Ion battery communications fail alarm 
 
Clear AbnlCur Alm*: Clears an abnormal current alarm. 
 
Clear Cur Imb Alm*: Clears a current imbalance alarm. 
 
ClrBatTestFail*: Clears a battery test fail alarm. 
LVD 
LVD Unit Menu 
Menu Navigation: Main Menu / Manual / LVD / LVD Unit 
Note: For WEB Interface; menu items are found under Device Information / LVD Group / LVD Unit 
/ select the Control tab. 
"LVD Unit" Parameter Settings: 
 
LVD1 Control: Temporarily connects or disconnects LVD1. Setting returns to original 
when Controller is returned to the Auto mode. 
 
LVD2 Control: Temporarily connects or disconnects LVD2. Setting returns to original 
when Controller is returned to the Auto mode. 
EIB 
EIB 1 Menu 
Menu Navigation: Main Menu / Manual / EIB / EIB1 
Note: For WEB Interface; menu items are found under Device Information / EIB Group / EIB 1 / 
select the Control tab. 
"EIB 1" Parameter Settings: (EIB1 refers to the first Extended Interface Board (EIB) in the 
system.)) 
 
Relay Output 9 through 13: Temporarily sets the relay to active or not active. Setting 
returns to original when Controller is returned to the Auto mode. 
Converter 
All Conv Ctrl Menu 
Menu Navigation: Main Menu / Manual / Converter / All Conv Ctrl 
Note: For WEB Interface; menu items are found under Device Information / Converter Group / 
select the Control tab. 
"All Conv Ctrl" Parameter Settings: 
 
Converter Trim: Temporarily sets the output voltage for all converters. Setting reverts to 
original when Controller is returned to the Auto mode. 
 
DC On/Off Ctrl: Temporarily turns the DC output on or off for all converters. Setting returns 
to original when Controller is returned to the Auto mode. 
 
Conv LED Control: Temporarily sets whether or not a converter
’s local power indicator 
blinks when the Controller is communicating with the converter. Setting returns to original 
when Controller is returned to the Auto mode.