Chapter 5.  Accessing the Controller via a Network Management System (NMS) 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
 
Ident Group 
Controller Ident Group 
 
identManufacturer 
The name of the equipment manufacturer. 
identModel 
The manufacturers model designation of the power system. 
identControllerFirmwareVersion 
The firmware (software) version of the Controller. 
identName 
The name of the power plant. This object should be set by the 
administrator. 
R/W 
System Group 
Controller System Value Group 
systemStatus 
Status of the complete plant (highest alarm). One of... 
(1) unknown - status has not yet been defined 
(2) normal - there are no activated alarms 
(3) warning - OA, lowest level of 'abnormal' status 
(4) minor - A3 
(5) major - MA 
(6) critical - CA, highest level of 'abnormal' status 
(7) unmanaged 
(8) restricted 
(9) testing 
(10) disabled 
systemVoltage 
System voltage, stored as mV. 
systemCurrent 
System current, stored as mA. 
systemUsedCapacity 
Used capacity, stored as percentage of the total capacity . 
psBattery Group 
Power System Battery Group 
psBatteryVoltage 
Battery voltage, stored as mV. 
psBatteryCurrent 
Battery current, stored as mA. 
psInput Group 
Power System Input Group 
psInputLineAVoltage 
The AC line A voltage, stored as mV. 
psInputLineBVoltage 
The AC line B voltage, stored as mV. 
psInputLineCVoltage 
The AC line C voltage, stored as mV. 
psTemperature Group 
Power System Temperature Group 
psTemperature1 
The first route temperature, stored as 0.001 Celsius degree. 
psTemperature2 
The second route temperature, stored as 0.001 Celsius degree.