Chapter 1.  Introduction 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
1.3.3 
System Components Monitoring and System Alarms Generation 
The ACU+ Controller monitors the components comprising the system (such as the rectifiers, converters, 
and supervisory modules) and generates alarms if a fault condition occurs. The ACU+ Controller also 
maintains an alarm history log. 
The available system alarms are programmed with an Alarm Severity Level. Each Alarm Severity Level 
has different visual/audible alarm attributes. Available Alarm Severity Levels and their attributes are listed 
in Table 1. 
Alarm 
Severity Level 
ACU+ Red 
Alarm Indicator 
ACU+ Yellow 
Alarm Indicator 
ACU+ 
Audible Alarm 
Critical Alarm (CA) 
ON 
OFF 
ON 
Major Alarm (MJ) 
ON 
OFF 
ON 
Minor Alarm (MN) 
OFF 
ON 
OFF 
No Alarm 
OFF 
OFF 
OFF 
Table 1 
Alarm Severity Levels 
 
The alarm indicator turns OFF if the fault(s) that triggered the alarm clears. 
 
The audible alarm can be silenced by pressing any key on the ACU+ Controller local interface pad. 
The audible alarm is also silenced if the fault(s) that triggered the alarm clears. 
 
An audible alarm cutoff feature can be programmed that silences the audible alarm after a pre-set 
programmable time period. The audible alarm can also be disabled. 
The available system alarms can also be mapped to alarm relays (located on ACU+ interface boards) that 
can be wired to external alarm circuits. 
1.3.4 
Operating Data Acquisition and Data Logs 
The ACU+ Controller acquires and anal
yses real time data from the system’s components such as the 
rectifiers, converters, and supervisory modules. 
The ACU+ Controller uses this data to process alarms and also records data in logs. The logs are viewed 
using the WEB Interface and consists of... 
 
Alarm History Log: records 600 latest alarms. 
 
Data History Log: records 60000 latest history data. 
 
Control Log: records 500 latest control events. 
 
System Log: records 3000 latest system events. 
 
Diesel Test Log: records 500 latest diesel test results. 
 
Battery Test Log: up to twelve (12) battery discharge tests can be performed and recorded per year. 
Note:  Once maximum number of log entries is reached, new entries overwrite oldest entries. 
Logs can be saved in the text (.txt) format.