IMPORTANT SAFETY WARNINGS 
(SAVE THESE INSTRUCTIONS) 
This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. 
Read this manual thoroughly before attempting to unpack, install, or operate your UPS. 
CAUTION!  To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive 
contaminants.    (Please see specifications for acceptable temperature and humidity range). 
CAUTION!  To reduce the risk of electric shock, do not remove the cover except to service the battery.    There are no user serviceable parts 
inside except for battery. 
CAUTION!  Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected. 
CAUTION!  The UPS must be connected to an AC power outlet with fuse or circuit breaker protection.    Do not plug into an outlet that is not 
grounded.    If you need to de-energize this equipment, turn off and unplug the unit. 
CAUTION!  To avoid electric shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a computer 
component. 
CAUTION!    To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit over current protection in 
accordance with the National Electric Code, ANSI/NFPA 70. 
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT!  CyberPower Systems does not sell products for life support or medical 
applications.  DO NOT use in any circumstance that would affect operation, safety of any life support equipment, any medical applications or 
patient care. 
DO NOT USE WITH OR NEAR AQUARIUMS!    To reduce the risk of fire or electric shock, do not use with or near an aquarium.    Condensation 
from the aquarium can cause the unit to short out. 
 
 
INSTALLING YOUR UPS SYSTEM   
 
 
UNPACKING 
Inspect the UPS upon receipt. The box should contain the following: 
(1) UPS unit; (1) User’s manual; (1) PowerPanel
®
 Personal Edition software CD; (1) USB device cable; (1) Telephone cable; (1) Warranty 
registration card; (1) Coaxial Cable 
 
WHAT IS AVR
 
The  CP685AVRLCD-G / CP825AVRLCD-G provide complete power 
protection from utility power that is not always consistent.  The 
CP685AVRLCD-G / CP825AVRLCD-G feature 890 Joules / 1030 Joules of 
surge protection, and provide long lasting battery backup during power 
outages with maintenance free batteries.  The CP685AVRLCD-G / 
CP825AVRLCD-G ensure consistent power to your computer system and 
include software that will automatically save your open files and shutdown 
your computer system during a utility power loss. 
 
AUTOMATIC VOLTAGE REGULATOR
 
The CP685AVRLCD-G / CP825AVRLCD-G stabilize utility power voltage 
levels that can be inconsistent.    The incoming utility power may be damaging 
to important data files and hardware, but with Automatic Voltage Regulation, 
the computer will not experience damaging voltage levels.    An Automatic 
Voltage Regulator automatically increases low or decreases high voltage to a 
consistent, computer safe 110v/120v.    The unit’s powerful battery will provide 
power only if the incoming voltage drops below 90v or increases above 140v. 
 
SYSTEM FUNCTIONAL BLOCK DIAGRAM 
 
 
 
 
 
 
 
 
 
 
HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT
 
1.  Ensure that the equipment plugged into the outlet does not exceed the UPS unit’s rated capacity (685VA/390W for CP685AVRLCD-G, 
825VA/450W for CP825AVRLCD-G).    If the rated capacities of the unit are exceeded, an overload condition may occur and cause the UPS 
unit to shut down or the circuit breaker to trip. 
2.  There are many factors that can affect the amount of power that your computer system will require.    It is suggested that the load you will be 
placing on the outlet not exceed 80% of the unit’s capacity. 
 
HARDWARE INSTALLATION GUIDE 
1.  Your new UPS may be used immediately upon receipt.    However, recharging the 
battery for at least 8 hours is recommended to ensure that the battery’s maximum 
charge capacity is achieved.    A loss of charge may occur during shipping and storage.   
To recharge the battery, simply leave the unit plugged into an AC outlet. 
2.  With the UPS unit off and unplugged, connect your computer, monitor, and any other 
peripherals requiring battery backup into the battery power supplied outlets.    Plug your 
other peripheral equipment (printer, scanner, speakers) into the full-time surge protection outlets.    DO NOT plug a laser printer, paper 
shredder, copier, space heater, vacuum, sump pump or other large electrical device into battery and surge protected outlets.    The 
power demands of these devices will overload and possibly damage the unit. 
3.  To protect a network connection from surges, connect a network cable into the IN jack of the UPS. Then 
connect a network cable from the OUT jack on the UPS to the network device. 
4.  Plug the UPS into a 2 pole, 3 wire grounding receptacle (wall outlet).    Make sure the wall branch outlet is 
protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air 
conditioner, refrigerator, copier, etc…).    The warranty prohibits the use of extension cords, outlet strips, and surge strips. 
5.  Press the power switch to turn the unit on.    The power on indicator light will illuminate and the unit will “beep”. 
6.  If an overload is detected, an audible alarm will sound and the unit will emit one long beep.    To correct this, turn the UPS off and unplug at 
least one piece of equipment from the battery power supplied outlets.    Make sure the circuit breaker is depressed and then turn the UPS on. 
7.  To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times. 
8.  To store your UPS for an extended period, cover it and store with the battery fully charged.    While in storage recharge the battery every three 
months to ensure battery life. 
 
BASIC OPERATION 
 
DESCRIPTION 
 
① 
Battery and Surge Protected Outlets 
The unit has four battery powered/surge suppression outlets for connected 
equipment to ensure temporary uninterrupted operation of your equipment during a 
power failure.( DO NOT plug a laser printer, paper shredder, copier, space heater, 
vacuum, sump pump or other large electrical device into battery and surge 
protected outlets.    The power demands of these devices will overload and 
possibly damage the unit.)
 
② 
Full-Time Surge Protection Outlets 
The unit has four surge suppression outlets which are always on 
③ 
Power Switch 
Press the power button to turn the UPS ON or OFF. 
④ 
Power On Indicator 
This LED is illuminated when the utility power is normal and the UPS outlets are providing power, free of surges and spikes. 
 
⑤ 
Electrical Wiring Fault Indicator 
This LED indicator will illuminate to warn the user that a wiring problem exists, such as bad ground, missing ground or reversed wiring.     
If this is illuminated, it is recommended to disconnect all electrical equipment from the outlet and have an electrician verify the outlet is 
properly wired. The unit will not provide surge protection without being plugged into a grounded and properly wired wall outlet. 
⑥ 
Communication Protection Ports 
Communication protection ports will protect any standard modem, fax, telephone line, network or Ethernet connection (RJ11/RJ45). 
⑦ 
Circuit Breaker 
Located on the side of the UPS, the circuit breaker serves to provide overload and fault protection.   
⑧ 
USB Port 
Allows for connection and communication between the USB port on the computer and the UPS unit.    The UPS communicates its status to 
the PowerPanel
®
 Personal Edition software.    This interface is also compatible with the Power Management provided by Windows
®
 Vista. 
Note: To install PowerPanel
®
 Personal Edition Software the computer will need Microsoft
R
  Internet Explore 6.0 or higher installed. 
⑨ 
Outlets Designed for AC Adapters 
The unit has four outlets spaced to allow AC power transfomers to be plugged into the UPS without blocking adjacent outlets. 
⑩ 
Coax/Cable/DSS Surge Protection 
The Coax/Cable/DSS surge protection ports will protect any cable modem, CATV converter, or 
DSS receiver. 
⑪ 
LCD Module Display 
Crystal Blue intelligent LCD panel shows all the UPS information using icons and messages.    For 
more information please check the “Definitions for Illumination LCD Indicators” section below. 
⑫ 
LCD Panel Toggle Switch 
The switch can be used to select the LCD panel displayed information including Input Voltage, 
Output Voltage and Estimated Run Time. The toggle frequency is set to one time per second. 
Holding the switch for more than two seconds while running on battery will silence the buzzer. 
 
 
DEFINITIONS FOR ILLUMINATED INDICATORS 
 
DEFINITIONS FOR ILLUMINATED LED INDICATORS 
 
 
Power ON 
 
Wiring Fault 
 
Alarm 
CONDITION 
On Off 
Off 
Normal 
On On/Off 
Two 
Beeps 
Utility Failure- The UPS is providing power to battery power-supplied outlets from 
the battery. 
On On/Off 
Rapid 
Beeps
Utility Failure- The UPS is providing battery power.    Rapid beeps indicate the unit 
will run out of power shortly. 
Off Off 
Long 
Beep 
System Overload- Occurs when connected equipment exceeds the rating of unit.   
Turn the UPS off, unplug at least one piece of equipment, wait 10 seconds, reset the 
circuit breaker and turn the unit on. 
Off On/Off 
Long 
Beep 
Battery Overload- Occurs when connected equipment exceeds the rating of battery 
outlets of the unit.    Turn the UPS off, unplug at least one piece of equipment from 
battery outlets, wait 10 seconds, reset the circuit breaker and turn the unit on. 
On/Off On 
None 
Electrical Wiring Fault- This indicates a wiring problem with the AC outlet such 
as bad ground, missing ground, or reversed wiring.    User is advised to disconnect 
all electrical equipment from the outlet and have an electrician check the outlet to 
verify proper wiring. 
 
DEFINITIONS FOR ILLUMINATED LCD INDICATORS 
 
Line mode 
UPS Status Display 
Capacity Display 
Digital Value Display 
Select SW 
Press 
 
 
 
 
Load 
Cap. 
Battery 
Cap. 
Input 
Voltage 
Output 
Voltage 
Run 
Time 
of Load 
of Batt. 
Initial 
V X X --  V 
 
 
 
 
1st 
V X X --  V 
 
 
 
 
2nd 
V X X --  V 
 
 
 
 
3rd 
V X X --  V 
 
 
 
 
4th 
V X X --  X 
 
 
 
 
5th(Return) V X X --  V 
 
 
 
 
(Overload) 
-- -- -- -- -- -- -- 
“V” : light up,        “X” : go out,        “--“ : not available 
 
Battery mode 
 “V” : light up,    “X” : go out,    “--“ : not available 
 
INPUT voltage meter: 
This meter measures the AC voltage that the UPS system is receiving from the utility wall outlet. The UPS is designed, to 
continuously supply connected equipment with stable, 110/120 output voltage. In the event of a complete power loss, severe brownout, or 
over-voltage, the UPS relies on its internal battery to supply consistent 110/120 output voltage. The INPUT voltage meter can be used as a 
diagnostic tool to identify poor-quality input power. 
OUTPUT voltage meter: This meter measures, in real time, the AC voltage that the UPS system is providing to the computer during normal line 
mode, and battery backup mode. 
ESTIMATE RUN TIME: This displays the run time estimate of the UPS with the current battery capacity and load. 
NORMAL icon: This icon appears when the UPS is working under normal conditions. 
BATTERY icon: During a severe brownout or blackout, this icon appears and an alarm sounds (two short beeps followed by a pause) to indicate 
the UPS is operating from its internal batteries. During a prolonged brownout or blackout, the alarm will sound continuously. The 
BATT.CAPACITY meter will show one 20% capacity segment remaining to indicate the UPS's batteries are nearly out of power. You should save 
files and turn off your equipment immediately. 
OVER LOAD icon: This icon appears and an alarm sounds to indicate the battery-supplied outlets are overloaded. To clear the overload, unplug 
some of your equipment from the battery-supplied outlets until the icon turns off and the alarm stops. 
BATT. CAPACITY meter: This meter displays the approximate charge level, in 20% increments, of the UPS’s internal battery. During a blackout 
or severe brownout, the UPS switches to battery power, the BATTERY icon appears, and the charge level decreases. 
LOAD CAPACITY meter: This meter displays the approximate output load level, in 20% increments, of the UPS’s battery outlets
 
 
REPLACING THE BATTERY 
Replacement of batteries located in an OPERATOR ACCESS AREA
1. 
When replacing batteries, replace with the same number of the following battery: BP8-12 / BB for CP685AVRLCD-G; HR1234W / BB for 
CP825AVRLCD-G. 
2. 
CAUTION!    Risk of Energy Hazard, 12 V, maximum 8(BP8-12 for CP685AVRLCD-G) and 9(HR1234W CP825AVRLCD-G) Ampere-hour 
battery. Before replacing batteries, remove conductive jewelry such as chains, wrist watches, and rings.   
3. 
CAUTION!    Do not dispose of batteries in a fire. The batteries may explode; 
UPS Status Display 
Capacity Display 
Digital Value Display 
Select SW 
Press 
 
 
 
 
Load 
Cap. 
Battery 
Cap. 
Input 
Voltage 
Output 
Voltage 
Run 
Time 
of Load 
of Batt. 
Initial 
-- 
-- 
V  V    
1st X 
-- 
-- 
X V    V    
2nd X 
-- 
-- 
V X       V  
3rd X 
-- 
-- 
V     V 
4th X 
-- 
-- 
V     
5th(Return) 
-- 
-- 
V  V    
Press >3sec 
(Sound 
Disable) 
-- 
-- -- -- -- -- -- -- 
Press >3sec 
again 
(Sound Enable) 
-- 
-- -- -- -- -- -- -- 
(Overload) 
-- 
-- -- -- -- -- -- -- 
The LCD display indicates a variety 
of UPS operational conditions. All 
descriptions apply when the UPS is 
plugged into an AC outlet and turned 
on or when the UPS is on battery. 
EMI 
Filter 
Surge 
Suppressor
 
AVR 
Charger 
AC/DC 
Battery 
Inverter
Input 
Output
Normal Mode 
Battery Mode