An integrated, manually operated bypass unit ensures an 
uninterrupted supply to the connected loads in the case of 
maintenance and/or service work. The internal electronic part 
(with the exception of the metal-clad manual bypass) can be 
disconnected via the mains input miniature circuit breakers. 
 
Fig.: Table showing the level of redundancy depending on the installed 
modules and available output power 
2.2 
Technical Data 
Type rating 
PROTECT 1.M (system) 
max. 24 kVA (cos 
ϕ = 0.7 lag.) 
16800 W 
PROTECT 1.040 (module) 
4000 VA (cos 
ϕ = 0.7 lag.)  
2800 W 
UPS input 
 
 
3ph~ or 1ph~ / N / PE 
Rated connection voltage 
400 V / 230 Vac (3ph~) or 
230 V (1ph~) 
Voltage range without 
277 Vac – 520 Vac ±3% 
battery operation 
(Rectifier 3ph~) 
 
160 Vac – 300 Vac ±3% 
 (Rectifier 
1ph~) 
no
redundancy
n+1
(4 kVA)
 
n+2
(8 kVA)
 
n+3
(12 kVA)
 
n+4
(16 kVA)
 
n+5
(20 kVA)
 
modules
modules
modules
modules
modules 
module
Number of 
UPS modules
Load
- - -
no
redundancy
- - -
20 kVA
n+1
(4 kVA)
no
redundancy
- - -
16 kVA
n+2
(8 kVA)
n+1
(4 kVA)
no
redundancy
- - -
12 kVA
n+3
(12 kVA)
n+2
(8 kVA)
n+1
(4 kVA)
no
redundancy
- - -
8 kVA
n+4
(16 kVA)
n+3
(12 kVA)
n+2
(8 kVA)
n+1
(4 kVA)
no
redundancy
4
 
kVA
24 kVA