Battery 
Nominal DC voltage (intermediate circuit) 120 Vdc 
DC window 102 Vdc – 160 Vdc ±1% 
Trickle charge voltage
 
 
137 Vdc ±1% 
Battery charging current (max.) 3.5 Adc per UPS module 
 
Communication 
Interfaces RS232 
(Sub-D9) 
 
RS485 (Sub-D9 / RJ45) 
 Additionally: Communication slot 
for optional expansion cards (e.g. 
AS/400 / SNMP, etc.) 
Shutdown software on CD 
"CompuWatch" for all common 
operating systems, e.g. Windows, 
Linux, Mac, Unix, FreeBSD, 
Novell, Sun 
General data 
Classification 
VFI SS 111 acc. to IEC 62040–3 
double-conversion technology 
Total efficiency AC-AC 
PROTECT 1.M (system) 
> 88% 
PROTECT 1.040 (module) 
> 89% 
 
Inherent noise (1m distance) 
PROTECT 1.M (system) 
< 62 dB(A) 
PROTECT 1.040 (module) 
< 55 dB(A) 
Cooling type 
Forced air cooling through 
variable-speed fans 
Operating temperature range  0 °C to +40 °C 
 
Battery systems  
(recommended): 
 +15°C to +25°C 
Storage temperature range 
0°C to +40°C 
Relative humidity 
20% – 90%