Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001
Battery Operation
During battery operation, the load is supported by the inverters. The inverters are supplied by battery 
power, ensuring uninterrupted support to the load.
While the UPS is running in battery operation, a single-line diagram will appear on the screen with a 
green line indicating the power flow from the batteries through the main inverter to the load for as 
long as the batteries are energized.
CAUTION!
Do not open Q2, Q7 or Q8 when the UPS is in battery operation, as this action may result 
in a load drop or a failure of the UPS to support the load.
Breaker Identification
Q1 
UPS input breaker
Q5
Static bypass input breaker
Q2
UPS output breaker
Q7
Battery breaker 1
Q3
Manual bypass breaker
Q8
Battery breaker 2
Note
Only operate a breaker when the associated breaker lamp is on.
Battery
Delta inverter
Main inverter
Bypass Static Switch