Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001
Manual Bypass Operation
During manual bypass operation, the critical load is supplied directly by utility power, making it 
possible to isolate the UPS and the Bypass Static Switch for maintenance. 
A single-line diagram will appear on the screen, with an orange line indicating the power flow from 
the utility to the load via the Q3 breaker. 
Note
Battery power is not available as an alternate power source while the system is running 
in manual bypass operation.
CAUTION!
Do not open Q3 when the UPS is in manual bypass operation, as this action may result in 
a load drop or a failure of the UPS to support the load.
Breaker Identification
Q1 
UPS input breaker
Q5
Static bypass input breaker
Q2
UPS output breaker
Q7
Battery breaker 1
Q3
Manual bypass breaker
Q8
Battery breaker 2
Note
Only operate a breaker when the associated breaker lamp is on.
Main inverter
Delta inverter
Bypass Static Switch
Battery