A.10 I/Os 
The Tuba has: 
10 Digital Inputs 
6 Digital Outputs 
2 Analog Inputs 
A.10.1  Digital Input Interfaces (on GENERAL I/O port) 
Feature Details 
Connector 
Location 
Type of input 
 Optically isolated 
 Single ended 
 PLC level 
Input current 
Ω
=
2500
5
.
V
Vin
Iin
  
* Iin = 2.2 mA @ Vin = 12 V 
Input current 
for high speed 
inputs 5 & 6 
Ω
=
1250
5
.
V
Vin
Iin
 
* Iin = 4.4 mA @ Vin = 12 V 
High-level 
input voltage 
12 V < Vin < 30 V, 24 V typical 
Low-level 
input voltage 
 0 V < Vin < 6.5 V 
Minimum 
pulse width  
> 4 x TS, where TS is sampling time 
 
Execution time 
(all inputs): 
the time from 
application of 
voltage on 
input until 
execution is 
complete 
If input is set to one of the built-in functions — 
Home, Inhibit, Hard Stop, Soft Stop, Hard and Soft 
Stop, Forward Limit, Reverse Limit or Begin — 
execution is immediate upon detection:  
                0 < T < 4 x TS 
If input is set to General input, execution depends 
on program. Typical execution time: 
≅ 0.5 msec. 
High-speed 
inputs 5 & 6 - 
minimum pulse 
width, in high-
speed mode 
 
T < 5 
µsec 
Notes: 
Home mode is high-speed mode and can be 
used for fast capture and precise homing. 
High speed input has a digital filter set to 
same value as digital filter (EF) of main 
encoder. 
Highest speed is achieved when turning on 
optocouplers. 
2.
5
K
In
p
u
t R
e
tu
rn
 (
i)
DI
GI
NPUT
 
Digital Input Schematic 
DIGITAL INPUTS
Tuba Installation Guide 
Technical Specifications 
MAN-TUBIG (Ver. 1.3)
 
 
A-13