Nortel Networks 1000M Manuale Utente

Pagina di 458
Page 306 of 456
 Powering up the system and initial loading
NN43021-310
Standard 02.01
December 2007
Preparing to power up – DC
Procedure 53
Preparing to power up – DC
1
Set the AC service panel circuit breakers to each rectifier OFF.
2
Remove the DC power distribution fuses or set the distribution circuit 
breakers OFF.
3
Set all circuit breakers in the rear of each pedestal OFF.
4
Set the power supply switches in each module OFF.
5
Set the ringing generators in each IPE or PE module OFF.
6
Set the blower unit in each pedestal OFF.
7
Set all faceplate switches to ENB.
8
End of Procedure
Turning DC power ON
Follow Procedure 54 to turn the DC power on.
CAUTION
Verify that the safety grounds are properly connected.