Brocade DCX 8510-4 Backbone Hardware Reference Manual
53-1002177-05
Brocade DCX 8510-4 chassis removal and replacement
5
5. Display and record the manufacturer serial numbers.
Enter chassisShow; then copy the command output into the config-miscinfo.txt file.
“Factory Serial Num” and “Serial Num” are listed under “Chassis/WWN Unit 1.” If the current
WWN cards are the original cards, the factory serial number listed is the same as the chassis
serial number.
WWN cards are the original cards, the factory serial number listed is the same as the chassis
serial number.
switch:admin> chassisshow
Chassis Backplane Revision: 1F
SW BLADE Slot: 1
Header Version: 2
Power Consume Factor: -50
Factory Part Num: 60-0001532-03
Factory Serial Num: KP000000195
Manufacture: Day: 1 Month: 1 Year: 2007
Update: Day: 14 Month: 3 Year: 2012
Time Alive: 187 days
Time Awake: 3 days
<output truncated>
CHASSIS/WWN Unit: 1 (in same assembly as WWN Unit: 2)
Header Version: 2
Power Consume Factor: -3
Factory Part Num: 60-0001501-07
Factory Serial Num: FT02X805BE2
Manufacture: Day: 26 Month: 3 Year: 2007
Update: Day: 14 Month: 3 Year: 2009
Time Alive: 207 days
Time Awake: 3 days
<output truncated>
switch:admin>
6. Create a SAN “profile” by entering and recording the information provided by the following
commands:
•
nsShow
•
nsAllShow
•
switchShow -qsfp
•
fabricShow
Copy the command output into a text file named “SANbefor.txt.” After the Brocade DCX 8510-4
is restored to the fabric, this information can be used to verify that no unintentional changes
have occurred to the fabric.
is restored to the fabric, this information can be used to verify that no unintentional changes
have occurred to the fabric.
switch:admin> nsshow
Enter Pid COS PortName NodeName TTL
<output truncated>
switch:admin> nsallshow
12 Nx_Ports in the Fabric
<output truncated>
switch:admin> switchshow