Serious  personal  injury  could  occur  if  you 
connect your machine to the power source 
before  you  have  completed  the  setup  pro-
cess.  DO  NOT  connect  the  machine  to  the 
power source until instructed to do so.
Wiring
the Model g0503 is prewired for 220V 3-phase 
operation.  if  440  voltage  is  required,  rewire  the 
machine per the instructions on 
page 49, and fol-
low the circuit requirements on this page.
Amperage Draw
the Model g0503 has a 20 hp main motor and 
a  2  hp  hydraulic  pump  motor  that  will  draw  the 
following amps at 440V 3-phase:
Main Motor ............................................ 24 amps
hydraulic pump Motor .............................3 amps
circuit Breaker Requirements
install  the  machine  on  a  dedicated  circuit  to 
reduce  the  possibility  of  overloading  the  circuit 
and  tripping  the  circuit  breaker.  if  the  circuit 
breaker trips and the circuit is of the correct load 
capacity, have the circuit inspected by a qualified 
electrician. never use a larger circuit breaker than 
stated below, or you will increase the risk of fire.
Circuit Breaker .........................................30 amp
Minimum Wire Requirements
For  440V  3-phase  operation,  use  the  following 
type of wire:
wire ............................................. 10 ga. Copper 
we  recommend  running  thwn/thhn  grade 
insulated wire through rigid conduit and hardwir-
ing  into  a  locking  power  disconnect.  Consult  a 
licensed  electrician  for  information  on  local  and 
national electrical codes.
440v 3-phase
Serious  personal  injury  could  occur  if  you 
connect your machine to the power source 
before you have completed the set up pro-
cess.  DO  NOT  connect  the  machine  to  the 
power source until instructed to do so.
Wiring
the Model g0503 is prewired for 220V 3-phase 
operation.
Amperage Draw
the Model g0503 has a 20 hp main motor and 
a  2  hp  hydraulic  pump  motor  that  will  draw  the 
following amps at 220V 3-phase:
Main Motor ............................................48 amps
hydraulic pump Motor .............................6 amps
circuit Breaker Requirements
install  the  machine  on  a  dedicated  circuit  to 
reduce  the  possibility  of  overloading  the  circuit 
and  tripping  the  circuit  breaker.  if  the  circuit 
breaker trips and the circuit is of the correct load 
capacity, have the circuit inspected by a qualified 
electrician. never use a larger circuit breaker than 
stated below, or you will increase the risk of fire.
Circuit Breaker .........................................60 amp
Minimum Wire Requirements
For  220V  3-phase  operation,  use  the  following 
type of wire:
wire ...............................................6 ga. Copper 
we  recommend  running  thwn/thhn  grade 
insulated wire through rigid conduit and hardwir-
ing  into  a  locking  power  disconnect.  Consult  a 
qualified  electrician  for  information  on  local  and 
national electrical codes.
220v 3-phase
SEcTION 2: cIRcuIT REQuIREMENTS