Insys GSM 4.2 I4 11-02-01-03-01.038 Manuale Utente

Codici prodotto
11-02-01-03-01.038
Pagina di 69
INSYS GSM 4.2 I4 
Functions and their configuration 
 
50
 
Dez-06
 
6.3 
Alarm Functionality 
The device has four independent digital inputs for alarm detection. 
Alarms are triggered by connecting an alarm input to ground. The alarm input is on HIGH 
potential by a pull-up resistor in open state. During an alarm, the device can send an 
alarm message 
 
The alarm inputs are buffered, i. e. it is possible that up to five events per alarm input are 
temporarily saved and processed separately by the device. 
The processing is done by the order of the alarm inputs, i. e. that first all events from 
alarm input number one are processed, after that all events from input number two and 
so on. 
 
6.3.1 Querying the alarm inputs 
You can query the state of the alarm inputs via AT commands, SMS or DTMF.  
AT command 
Enter the command AT**IN? via a terminal program or the HSComm terminal window.  
The AT command will send the following response: 
OPEN   
Not activated, open 
CLOSE  
Activated, connected to ground 
SMS query  
The automatic processing of SMS messages must be enabled (see Chapter 6.2.3). 
DTMF query  
The processing of DTMF tones must be enabled (see Chapter 6.1.2). 
6.3.2 Alarm types 
Each of the two alarm inputs can be configured either as simple alarm input or als pulse 
input. This results in two different alarm inputs: 
  Simple alarm 
  Pulse alarm 
The characteristics and configuration of the alarms are described in the following.