Functions and their configuration 
 
Dez-06 
            51 
Simple alarm 
A simple alarm is triggered by changing the alarm input from HIGH to LOW/GND. The 
alarm is accepted after 0.3 seconds. Even if it is configured as pulse input, a simple alarm 
is triggered as soon as the input is connected to ground for at least 4 seconds – irrespec-
tive of the prior history.  
You can assign a message with a message text of max. 140 characters to the single 
alarm.  
 
Pulse alarm 
Sequences of up to 10 pulses can be detected as different alarms at the pulse input. 
Pulses and pauses may last from 0.3 to 2 seconds. 
 
 
You can assign each pulse alarm a message with the following design: 
  A group message text with max. 140 characters 
  A message text with max. 140 characters 
 
 
Note 
A collective message and a message may have only 140 characters 
altogether. 
The pulse input can be used particularly to transmit several alarm states from small PLCs 
like SIEMENS Logo!™, Crouzet Millenium™, Comat BoxX™ or Moeller Easy™. A demonstra-
tion program for creating such pulse sequences with the PLC Siemens Logo! is available 
on request (send e-mail to insys@insys-tec.de).  
6.3.3 Possible reactions to incoming alarms 
Depending on the alarm type you can configure the following functions for incoming 
alarms: