b) Connection to a Closed Loop System 
• Condenser water supply inlet is 1/2" female pipe thread (FPT). A minimum of 3/8" OD 
copper tubing is recommended for the condenser water supply line.
• Condenser return outlet is 3/8" FPT. A minimum of 3/8" OD hard pipe is recommended for 
the condenser return line.
• Shut-off valves and drain valves should be installed at both the condenser water supply 
inlet and condenser return outlet.
• The water supply to the condenser should not drop below 4 GPM. 
• The pressure differential between the condenser water supply inlet and condenser return 
outlet must be no less than 10 PSIG.
• When using a glycol blend, the solution mixture should be less than 30% glycol.
• In order to maintain the proper high side pressure, the condenser water supply inlet 
temperature should not drop below 45°F (7°C) and the condenser return outlet 
temperature must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker 
installation is complete, confirm the condenser return outlet temperature 5 minutes 
after a freeze cycle starts. If the outlet temperature is not in the proper range, adjust the 
water-regulating valve to bring it into range.
Condenser Return 
Line Shut-Off Valve
Condenser Return 
Line Drain Valve
Condenser 
Return Outlet 
3/8" FPT
Icemaker Water Supply 
Line Shut-Off Valve
Condenser Water Supply 
Line Shut-Off Valve
Condenser Water Supply 
Line Drain Valve
Condenser Water 
Supply Inlet
1/2" FPT
Drip Tray 
Drain Outlet 
3/4" FPT
Fig. 6
DCM-750BWH(-OS)
Connection to a Closed Loop System
Separate piping to approved drain. 
Leave a two-inch (5 cm) vertical air 
gap between the end of each pipe 
and the drain.
Two-inch 
(5 cm) air 
gap
Floor Drain
Icemaker
Stand
Icemaker Water 
Supply Inlet
1/2" FPT
Icemaker Water Supply 
Line Drain Valve
Storage Bin 
Drain Outlet 
3/4" FPT
Vent 
Tube