proDUCt DeSCription
 
The AmericaSeries  S1C/H  and  S2C 
condensing units are, air-cooled, vertically 
arranged  side  discharge,  high  efficiency 
units designed specifically to meet  or ex-
ceed a 13 SEER rating.  
 
The S1C 9,000-36,000 Btuh and S1H 
9,000-24,000 Btuh capacity condensing unit 
will provide cooling for a single evaporator, 
as identified in the "S1C Specifications and 
Dimensions" section on pages 23-24. 
 
The S2C 18,000 (99) - 21,000 (92) and 
23,000 (22) Btuh capacity condensing units 
will provide cooling for two evaporators, as 
identified  on page 25 in the "S2C Specifica-
tions and Dimensions" section.  The S1C/H 
and S2C  are quiet units that can be recom-
mended for both commercial and residential 
applications.
 
Installation  of  the  S1C/H  and  S2C 
condensing  units  is  simplified  by  a  24v 
control  interconnection from the evaporator 
and multiple units can be lined up in close 
proximity to an exterior wall. Service valves 
are  recessed  to  reduce  tampering  and 
all 9,000-12,000 Btuh units are equipped 
with a Duratec Performance Package that 
includes  an  oversized  suction  accumula-
tor  with  surge  baffles  and  enhanced  oil 
management, a factory installed solid core 
filter drier and loss of charge switch. A field 
installed crankcase heater is standard on 
S1H 09 &12 (Thermostatically controlled) 
models, and is available as optional equip-
ment on other models.
• Compressor and fan motor contactor
• Run capacitor
• Loss of charge switch (09 - 12 only)
• Low voltage terminal connections
•  Large  capacity  suction  accumulator 
(09 - 12 only)
• Solid core filter drier (09 - 12 only)
• Thermostatically controlled crankcase 
heater (09 - 12 S1H’s)
• H.P.S. (High pressure switch)
- Standard on S1H’s (heat pumps)
- Standard on S1C’s 18K and above.
•  Low Ambient  controls
  for  operation  
down  to  32º  F  standard,  factory  in-
stalled 
on all S1H’s (heat pumps)
•  Field  installed  crankcase  heater 
for  straight  cool  units  (standard  on 
9,000-12,000 Btuh S1H’s Thermostati-
cally controlled)
•  Straight  cool  hard  start  (standard  on 
all S1H’s)
• 115v (9,000-12,000 Btuh only) 
• Copper/copper coils (sea coast use)
•  Low Ambient controls 
for operation down 
to 32º F, specify this option for S1C or 
S2C systems (standard on S1H’s) that 
will  be  operated  in  cooling  mode  at 
outside temperatures below 60º F
 (field 
installed kit)
• Low Ambient for operation down to 0º F 
for S1C, S1H or S2C systems (consult 
factory for availability)
inStaller SUpplieD itemS
• Power wiring
• Low volt wiring (18 awg minimum)
• Secure mounting pad or foundation
•  Refrigerant  piping  (if  not  purchased 
from EMI)
• High Volt Disconnect
•  Refrigerant  for  charging  interconnect 
piping (see charge table on page 10)
itemS For ConSiDeration
low ambient controls are required when 
the system is asked to cool at outdoor tem-
peratures below 60º F, this may cause dam-
age to the compressor and coil, and  may 
Thermostatically  controlled  crankcase 
heater
 – This feature energizes the crank-
case  heater  only  when  needed,  removes 
the  heater  from  the  electrical  circuit  at 
conditions  where  it’s  not  required,  saving 
unnecessary Watts, and increasing overall 
system efficiency. 
ControlS anD ComponentS
(Factory Installed or Supplied)
SYStem optionS