Side Discharge Condensers
5
inStallation inStrUCtionS
Unit moUnting inStrUCtionS
Continued
5.  Insert  lag  bolts  through  the  holes  in 
the  bottom  of  the  unit  and  tighten  to 
secure. 
6. Insert lag bolts through the holes in the 
feet on the back of the unit and tighten 
to secure. 
7. Replace the front panel, do not tighten 
the side screws at this time.
  
     
Lag Bolts
Compressor 
 
         
  
Accumulator             
  
 Capacitor
Filter Drier
  
3. Use only HACR type breakers or time 
delay fuses. Select the wire size accord-
ing to the ampacity rating. 
4.  To  access  electrical  connections  and 
wiring diagram:
a) Remove the screws on the side panel 
adjacent to the back panel.
R
ating 
Plate
eleCtriCal Wiring
1. All electrical wiring must be run accord-
ing to NEC and local codes. 
2. Refer to the unit rating plate for voltage, 
minimum circuit ampacity and over cur-
rent protection requirements. 
b)  The  screws  adjacent  to  the  front 
panel should already be loose (don't 
remove them).
S1C
Shown
S1C
Shown