Setting Up a Changeover Bypass Zone
To set up a changeover bypass zone:
1. From the Home screen, press the Setup icon. The System Manager Setup or 
Coordinator Setup and Status screen appears.
2. For a System Manager, press the Systems button, then select the coordinator 
that contains the zone you want to configure. The Coordinator Setup and Status 
screen appears.
For a Coordinator, press the Systems button. The System Setup and Status 
screen appears.
3. Press the Zones button. The Zones Setup and Status screen appears.
4. Press the Setup button. The Summary of Zone Controllers appears.
5. Select the zone. The Zone Setup screen appears.  
Figure 42: Zone Setup Screen
ZC6 - Zone Setup
Voting: 
Thermostat Warm / Cool 
Adjust: 
Temporary Occupancy 
Input:
FI
G
:Zne
S
tu
p
Enabled
Select value to modify.
Edit Zone Name
Heating Unocc Setpoint:
Heating Occ Setpoint:
Cooling Occ Setpoint:
Cooling Unocc Setpoint: 
62.0 Deg F
Zone Status
Copy Zone Setup to 
All Other Zones
Enabled
Enabled
68.0 Deg F
72.0 Deg F
78.0 Deg F
Max Damper
Position: 
Heating Min Damper
Position: 
Cooling Min Damper
Position:
20.0%
20.0%
95.0%