York YKSMU2x0-0 Manuale Utente

Pagina di 96
System Manager/Zone Coordinator User’s Manual
62
428516-YUM-B-0908
6. Press the button for the zone parameter you want to change. The button label 
describes the current setting. When you press the button, the appropriate screen 
appears, allowing you to change the value. Table 15 lists these parameters and 
their ranges or possible selections. 
a. If you want to edit the name of the zone, press the Edit Zone Name button. 
On the Zone Name screen that appears, use the on-screen keyboard to enter 
a new name. Click OK to save.
b. If you want to apply these zone settings to all zones currently defined, press 
the Copy Zone Setup to All Other Zones button. A confirmation message 
appears. Press OK to perform the copy operation.
7. After you complete the zone setup changes, press OK. The Zone Setup screen 
returns, reflecting the changes you made.
Setting Up a CV RTU Zone
To set up a CV RTU zone:
1. From the Home screen, press the Setup icon. The System Manager Setup 
screen appears.
2. Press the Systems button, then select the CV RTU that contains the zone you 
want to configure. The CV RTU Setup and Status screen appears.
Table 15: Zone Setup Parameters
Parameter
Parameter Range/Selections
Voting
Enabled or Disabled
Heating Unocc Setpoint
Valid range 55.0 to 70.0 Deg F
1
1.
Heating Unoccupied <= Heating Occupied <= Cooling Occupied <= Cooling Unoccupied
Thermostat Warm / Cool Adjust
Enabled or Disabled
Heating Occ Setpoint
Valid range 62.0 to 75.0 Deg F
Temporary Occupancy Input
Enabled or Disabled
Cooling Occ Setpoint
Valid range 68.0 to 88.0 Deg F
Cooling Unocc Setpoint
Valid range 75.0 to 90.0 Deg F
Max Damper Position
Valid range 0 to 100%
2
2.
Minimum position <= Maximum Position
Heating Min Damper Position
Valid range 0 to 100%
Cooling Min Damper Position
Valid range 0 to 100%