York YKSMU2x0-0 Manuale Utente

Pagina di 96
System Manager/Zone Coordinator User’s Manual
64
428516-YUM-B-0908
Setting up a VAV RTU Zone
To set up a VAV RTU zone:
1. From the Home screen, press the Setup icon. The System Manager Setup or 
Coordinator Setup and Status screen appears.
2. For a System Manager, press the Systems button, then select the coordinator 
that contains the zone you want to configure. The Coordinator Setup and Status 
screen appears.
3. Press the Zones button. The Zones Setup screen appears.
4. Press the Setup button. A summary of zones appears.
5. Select the zone. The Zone Setup screen appears. 
Figure 44: VAV RTU Zone Setup Screen
VAV 24 - Zone Setup
Thermostat Warm / Cool 
Adjust: 
Temporary Occupancy 
Input:
Supply Area:
Supply Pickup Gain:
Heating Unocc Min 
Flow:
Heating Occ Min 
Flow:
Cooling Occ Min 
Flow:
Cooling Unocc Min 
Flow:
F
IG
:Z
n
e
S
tu
p
VAV
Heating Unocc Setpoint:
Heating Occ Setpoint:
Cooling Occ Setpoint:
Cooling Unocc Setpoint:
Cooling Max Flow:
Warm-up Min Flow:
CO2 Ventilation Cutoff:
Box Mode: 
Select value to modify.
Edit Zone Name
Zone Status
Copy Zone Setup to 
All Other Zones
62.0 Deg F
68.0 Deg F
72.0 Deg F
78.0 Deg F
530 cfm
200 cfm
700 ppm
Enabled
0.184 sq ft
Enabled
2.896
200 cfm
265 cfm
53 cfm
0 cfm
Auto