Siemens M200D Manuale Utente

Pagina di 114
 
Installation / connection 
 
4.2 Connection 
M200D AS-Interface Basic 
Manual, 03/2009, A5E01668085-01 
55
 
4.2 
Connection 
 
 
More connection technology products can be found in "Siemens Solution Partners" 
) under "Distributed Field Installation System".     
4.2.1 
Required components/cables 
Selecting the power cables    
 
DANGER 
 
Hazardous voltage 
Can Cause Death, Serious Injury, or Property Damage 
Before starting work, disconnect the system and devices from the power supply. 
 
 
The cross-section of the power cables must be suitable for the prevailing ambient conditions. 
The following factors determine the cross-section: 
●  The current set on the device 
●  The cable installation type 
●  The ambient temperature 
●  The type of material (PVC, rubber) 
The following maximum current-carrying capacities apply for PVC power cables when 
installed, for example, in the cable duct (depending on the ambient temperature): 
 
Cross-section  T
U
 = 30 °C 
T
U
 = 40 °C 
T
U
 = 45 °C 
T
U
 = 50 °C 
T
U
 = 55 °C 
1.5 mm
2
 
14 A 
12.2 A 
11.1 A 
9.9 A 
8.5 A 
2.5 mm
2
 
19 A 
16.5 A 
15.0 A 
13.5 A 
11.6 A 
4.0 mm
2
 
26 A 
22.6 A 
20.5 A 
18.5 A 
15.9 A