Installation / connection
4.2 Connection
M200D AS-Interface Basic
Manual, 03/2009, A5E01668085-01
Manual, 03/2009, A5E01668085-01
55
4.2
Connection
More connection technology products can be found in "Siemens Solution Partners"
) under "Distributed Field Installation System".
4.2.1
Required components/cables
Selecting the power cables
DANGER
Hazardous voltage
Can Cause Death, Serious Injury, or Property Damage
Before starting work, disconnect the system and devices from the power supply.
Can Cause Death, Serious Injury, or Property Damage
Before starting work, disconnect the system and devices from the power supply.
The cross-section of the power cables must be suitable for the prevailing ambient conditions.
The following factors determine the cross-section:
● The current set on the device
● The cable installation type
● The ambient temperature
● The type of material (PVC, rubber)
The following maximum current-carrying capacities apply for PVC power cables when
● The current set on the device
● The cable installation type
● The ambient temperature
● The type of material (PVC, rubber)
The following maximum current-carrying capacities apply for PVC power cables when
installed, for example, in the cable duct (depending on the ambient temperature):
Cross-section T
U
= 30 °C
T
U
= 40 °C
T
U
= 45 °C
T
U
= 50 °C
T
U
= 55 °C
1.5 mm
2
14 A
12.2 A
11.1 A
9.9 A
8.5 A
2.5 mm
2
19 A
16.5 A
15.0 A
13.5 A
11.6 A
4.0 mm
2
26 A
22.6 A
20.5 A
18.5 A
15.9 A