Consumer connection on the motor starter
For the assignment of X2, see Power terminal (Page 58):
● A flexible Cu cable with 1.5 mm
● A flexible Cu cable with 1.5 mm
2
or 2.5 mm
2
– Without brake control: 3 wire + PE
– With brake control: 5 wire + PE
– With temperature sensor: 2 additional wires
– Han Q8/0 pin power connector
– With brake control: 5 wire + PE
– With temperature sensor: 2 additional wires
– Han Q8/0 pin power connector
Item
Order no.
Connector set, 8 X 1.5 mm
2
, 9 pin, complete with PG16 cable entry
3RK1902-0CE00
Connector set, 8 X 2.5 mm
2
, 9 pin, complete with PG16 cable entry
3RK1902-0CC00
4.2.3
Installing and wiring power connectors
DANGER
Hazardous voltage
Can Cause Death, Serious Injury, or Property Damage
Before starting work, disconnect the system and devices from the power supply.
Can Cause Death, Serious Injury, or Property Damage
Before starting work, disconnect the system and devices from the power supply.
Installa and wire the power connectors as follows:
Step
Procedure
Route the cable through the cable gland, sealing insert (enclosed), and the connector housing. The sealing
Route the cable through the cable gland, sealing insert (enclosed), and the connector housing. The sealing
insert is available in the following gradings:
Permissible external diameter of the cable
Permissible external diameter of the cable
Sealing insert
1
7.0 to 10.5 mm
9.0 to 13.0 mm
11.5 to 15.5 mm
Green
Red
White
2
Strip the cable over a length of 20 mm.
3
Strip the cores over a length of 8 mm.
4
Secure the contact sockets/pins on the cores by crimping or soldering them.
5
Sort the contact sockets/pins in the socket/pin insert in accordance with the assignments (see section Power
terminal (Page 58)). The contact sockets/pins should not engage yet. Make sure that they are correctly
assigned. Push the contact sockets/pins into the socket/pin insert until they engage. Use a suitable tool to
remove contact sockets/pins that have already been installed (Han Q4/2: 3RK1902-0AB00, Han Q8/0:
3RK1902-0AJ00.
6
Make sure that the position of the coding is correct, pull the cable back, and secure the socket/pin insert in the
connector housing using the cross-recessed screws enclosed.
7
Secure the cable gland. When doing so, make sure that the cable is not twisted against the connector housing.