Diagnostics 
 
7.4 Diagnostics with the addressing and diagnostics unit 
M200D AS-Interface Basic 
Manual, 03/2009, A5E01668085-01 
87
 
7.4 
Diagnostics with the addressing and diagnostics unit 
Diagnostics functions    
The addressing and diagnostics unit (order no.: 3RK1904-2AB01) features a range of 
diagnostics functions, such as: 
●  Detecting incorrect polarity or overload 
●  Measuring the AS-i supply voltage 
●  Detecting faults (with comments) 
●  Displaying I/O faults 
For more information, refer to the operating instructions for the addressing and diagnostics 
unit. 
 
7.5 
Troubleshooting 
7.5.1 
Response to faults 
Description    
In some cases, the device can be set in such a way that it responds to faults by either 
issuing an alarm or by shutting down. Examples: "Response to asymmetry", "response to 
temperature sensor overload". 
The following table shows how the motor starter responds (depending on how it has been 
parameterized): 
 
Fault 
 
Response 1 
Response 2 
Response: 
Alarm 
Shutdown 
Message bit: 
Group alarm set 
Group fault set 
LED display: 
DEVICE flashes yellow 
DEVICE lights up yellow 
SF lights up red 
Motor and brake: 
Not shut down 
Shut down 
 
 
 
Note 
With certain faults (e.g. "process mapping error" or device faults, such as "Contact block 
defective"), however, the device always responds by shutting down. 
This response cannot be changed.