INSTALLATION
Thermostat Wire Table
OPTIONAL WALL 
THERMOSTAT 
A wall thermostat may be installed if desired. 
Connect the wires as per the wiring diagrams on 
page 13.  Use table on this page  to determine 
the maximum wire length:
Note: Preferable if the thermostat is installed 
on an interior wall.
Regency offers an optional programmable 
thermostat but any 250-750 millivolt rated non-
anticipator type thermostat that is CSA, ULC or 
UL approved may be used.
CAUTION
Do not connect the millivolt 
wall thermostat wires 
to the 120V wires.
OPTIONAL REMOTE 
CONTROL 
Use the Regency Remote Control Kit  approved 
for this unit. Use of other systems may void 
your warranty.
The remote control kit comes with a hand held 
transmitter, a receiver and a wall mounting 
plate.
1)  Choose a convenient location on the wall 
to install the receiver and the receptacle 
box (protection from extreme heat is very 
important). Run wires from the fi replace to 
that location, use Thermostat Wire Table.
2)  Connect the wires as per the wiring diagram 
above.
CAUTION
Do not connect the millivolt re-
mote control wires to 
the 120V wires.
3)  Install 3 AAA alkaline batteries in transmitter 
and 4 AA alkaline batteries in  the receiver. 
Install the receiver and its cover in the wall. 
Switch the  remote receiver to "remote" 
mode. The remote control is now ready for 
operation.
FINAL CHECK
Before leaving this unit with the customer, the 
installer must ensure that the appliance is fi ring 
correctly. This includes:
1)  Clocking the appliance to ensure the cor-
rect fi ring rate (rate noted on label) at 15 
minutes.
2)  If required, adjusting the primary air to ensure 
that the fl ame does not carbon. First allow 
the unit to burn for 15 min. to stabilize.
CAUTION
Any alteration to the product that causes 
sooting or carboning that results in damage 
to the exterior facia is not the responsibility 
of the manufacturer.
3)  Ensuring that the appliance is venting cor-
rectly. See page 8.
14 GA.
16 GA.
18 GA.
20 GA.
22 GA.
50 Ft.
32 Ft.
20 Ft.
12 Ft.
9 Ft.
Recommended Maximum Lead Length 
(Two-Wire) When Using Wall 
Thermostat (CP-2 System)
Wire Size                       Max. Length