Installation
C
HIMNEY
 I
NSTALLATION
 T
HROUGH
 W
ALL
:
Here are four methods of combustible wall chimney connector pass-throughs. This information was provided from 
NFPA 211.
Method  A.  12”  (304.8  mm)  Clearance  to  Combustible  Wall 
Member:  Using  a  minimum  thickness  3.5”  (89  mm)  brick  and 
a  5⁄8”  (15.9  mm)  minimum  wall  thickness  clay  liner,  construct  a 
wall  pass-through.    The  clay  liner  must  conform  to  ASTM  C315 
(Standard Specification for Clay Fire Linings) or its equivalent. Keep 
a  minimum of  12”  (305  mm)  of  brick  masonry  between  the  clay 
liner and wall combustibles.  The clay liner shall run from the brick 
masonry outer surface to the inner surface of the chimney flue liner 
but not past the inner surface.  Firmly grout or cement the clay liner 
in place to the chimney flue liner.  
Method  B.  9”  (229  mm)  Clearance  to  Combustible  Wall  Member: 
Using a 6” (152 mm) inside diameter, factory-built Solid-Pak chimney 
section with insulation of 1” (25.4 mm) or more, build a wall pass-
through with a minimum 9” (229 mm) air space between the outer 
wall of the chimney length and wall combustibles. Use sheet metal 
supports fastened securely to wall surfaces on all sides, to maintain 
the 9” (229 mm) air space.  When fastening supports to chimney 
length, do not penetrate the chimney liner (the inside wall of the 
Solid-Pak chimney). The inner end of the Solid-Pak chimney section 
shall  be  flush  with  the  inside  of  the  masonry  chimney  flue,  and 
sealed with a non-water soluble refractory cement. Use this cement to also seal to the brick masonry penetration.
A
D
C
B
Method C. 6” (152.4 mm) Clearance to Combustible Wall Member: 
Starting with a minimum 24 gauge (.024” [0.6 mm]) 6” (152.4 mm) 
metal chimney connector, and a minimum 24 gauge ventilated wall 
thimble which has two air channels of 1” (25.4 mm) each, construct 
a  wall  pass-through.  There  shall  be  a  minimum  6”  (152.4  mm) 
separation  area  containing  fiberglass  insulation,  from  the  outer 
surface of the wall thimble to wall combustibles. Support the wall 
thimble,  and  cover  its  opening  with  a  24  gauge  minimum  sheet 
metal  support.  Maintain  the  6”  (152.4  mm)  space.  There  should 
also be a support sized to fit and hold the metal chimney connector. 
See that the supports are fastened securely to wall surfaces on all 
sides. Make sure fasteners used to secure the metal chimney connector do not penetrate chimney flue liner.  
Method D.  2” (50.8 mm) Clearance to Combustible Wall Member: 
Start with a solid-pak listed factory built chimney section at least 
12” (304 mm) long, with insulation of 1” (25.4 mm) or more, and 
an inside diameter of 8” (2” [51 mm] larger than the 6” [152.4 mm] 
chimney connector). Use this as a pass-through for a minimum 24 
gauge single wall steel chimney connector. Keep solid-pak section 
concentric with and spaced 1” (25.4 mm) off the chimney connector 
by  way  of  sheet  metal  support  plates  at  both  ends  of  chimney 
section.  Cover opening with and support chimney section on both 
sides with 24 gauge minimum sheet metal supports. See that the 
supports are fastened securely to wall surfaces on all sides. Make 
sure fasteners used to secure chimney flue liner.
NOTES:
1. Connectors to a masonry chimney, excepting method B, shall extend in one continuous section through the wall 
pass-through system and the chimney wall, to but not past the inner flue liner face.
2. A chimney connector shall not pass through an attic or roof space, closet or similar concealed space, or a floor, 
or ceiling.