Enviro 2100 Manuale Utente

Pagina di 20
Installation
I
NSTALLATION
:
A  non-combustible  floor  protector  is  required  under  all  freestanding  units,  refer  to  “Clearances  To 
Combustibles - Freestanding”. When venting into a masonry chimney the floor protector must be installed 
directly below the chimney vent and 2” (50.8 mm) on either side of the chimney vent.
Vent the stove into a clean, lined, approved masonry chimney in good condition, conforming to local 
building codes or a listed 6” (150 mm) factory built chimney suitable for use with solid fuels and conforming 
to, ULC-S629 in CANADA or UL-103HT in the U.S.A.. Connect the stove to this chimney with a short and 
straight 6” (150 mm), 25 gauge or heavier, single wall black or blued steel smoke pipe. Connection to all 
masonry chimneys must be a metal or masonry thimble cemented in place. All smoke pipes must slope 
upwards, all connections must be tight and secured with three sheet metal screws equally spaced. The 
smoke pipe length should not exceed 40% of the chimney height above the stove. 
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
���������
�����
��������
����� ������ �� �����
���������
��������
���
������� ��� ����������
������� ���� �� �����
�� ����
����� ��
�������
��� �������� �� ������ ���� �� ����� ����� ���� �
�� ���� ��� ��������� ����� ����� ���� ��� �������
��������� �� ��� ��� �� ��� ��������
������� �������� ��������������� �������
�� ������ ��� ���� �� �������� �� ������
������ �� ������ ������ ����
������� ����������
NOTE: In installations where there is constant or frequent high winds, install a flue damper to reduce 
the effect that high winds have on increasing the draft.  A significant increase in draft due to high winds 
may cause your unit to overfire, which could be hazardous and will void the warranty.
12