To Use the Vent Graph (Figure 17)
1.  Determine the height of the center of the horizontal vent 
pipe. Using this dimension on the Sidewall Vent Graph, 
locate  the  point  it  intersects  with  the  slanted  graph 
line.
2.  From the point of this intersection, draw a vertical line 
to the bottom of the graph.
3.  Select the indicated dimension, and position the unit in 
accordance with same.
EXAMPLE A:
If the vertical dimension from the floor of the unit is 35 feet, 
the horizontal run to the outer wall flange must not exceed 
6.5 feet.
EXAMPLE B:
If the vertical dimension from the floor of the unit is 6.5 
feet, the horizontal run to the outer wall flange must not 
exceed 14.5 feet.
Special Note: For  each 45 degree elbow installed in the 
horizontal run, the length of the horizontal run MUST be 
reduced by 18" (45cm). This does not apply if the 45 degree 
elbows are installed on the vertical part of the vent system. 
Reduce 3' for every 90° elbow.
Example: According to the chart the maximum horizontal 
vent length is 20' and if two 45 degree elbows are required 
in the horizontal vent it must be reduced to 17'.
The maximum number of 45 degree elbows permitted per 
side wall installation is two (2). These elbows can be installed 
in either the vertical or horizontal run.
Note:  On  vertical  venting  the  first  elbow  does  not  get 
counted.
Note:  Flue  heat  shield  must  be  installed  for  venting 
applications with less than two feet of vertical pipe off the 
top of the fireplace.
Figure 17
  Acceptable vertical and horizontal vent run.
 
(40' maximum vertical and 20' maximum horizontal)
  Unacceptable vertical and horizontal vent run.
Venting Graph (Dimensions in Feet)
VENTING FIREPLACE - TOP
TOP EXIT - VERTICAL AND HORIZONTAL TERMINATION
(DIMENSIONS IN FEET)
VER
TICAL
DIMENSION
FROM
THE
BOTT
OM
OF
THE
UNIT
TO
THE
CENTER
OF
THE
FLUE
OUTLET
WITH
VER
TICAL
OR
HORIZONT
AL
TERMINA
TION
CAPS
TOP VENT
CONNECTION
HORIZONTAL RUN
FLUE HEAT
SHIELD
REQUIRED