Mantel Chart (Figure 3)
Figure 3
Clearances (Figure 4)
Clearance from top front edge of fireplace to ceiling is 36"
Clearance from side of fireplace to adjacent sidewall is 6".
36”
(914mm)
6” (152mm)
Figure 4
Figure 5
Note:  Island (C) and Room Divider (F) 
installation  is  possible  as  long  as  the 
horizontal portion of the vent system 
(H)  does  not  exceed  20  feet  with  a 
minimum  vertical  run  of  8  feet.  See 
details in Venting Section.
When  you  install  your  Direct  Vent 
Fireplace in (F) Room divider or (A) Flat 
on wall corner positions, a minimum of 
6 inches clearance must be maintained 
from  the  perpendicular  wall  and  the 
front edge of the appliance.
Figure 2
Combustible Material
No greeting cards, stockings or ornamentation of any type should 
be placed on or attached to the fireplace. The flow of heat can 
ignite combustibles.
(A) CORNER
INSTALLATION
(E) ANGLED CORNER
INSTALLATION
(C) ISLAND
INSTALLATION
(B) CABINET
INSTALLATION
(F) ROOM DIVIDER
INSTALLATION
(D) FLUSH WALL
INSTALLATION
Clearance to Combustibles
Back
0" (0 mm)
Side
0" (0 mm)
Floor
0" (0 mm)
Top Stand-off
0" (0 mm)
Top Framing Edge
6" (152 mm)
GLASS FRONT
6”
SEE MANTLE CHART FOR
MAXIMUM MANTLE DEPTH
2” x 4” HEADER
STAND OFF
6” (152mm) HEIGHT
ABOVE TOP OF
FIREPLACE
NAILING
FLANGES
TOP FRAMING
LEDGE
NON-COMBUSTIBLE
FIRST 6” (SEE
MAGNIFIED VIEW)
FINISHED WALL
(COMBUSTIBLE)
SEE MANTLE CHART
FOR MINIMUM HEIGHT
OF MANTLE ABOVE UNIT
CLEARANCES
LOCATING FIREPLACE
MANTEL
19”
18 3/4”
17”
16”
15”
14”
13”
12”
11”
10”
2 1/4”
1 1/2”
3/4”
8”
6”
4 1/2”
3 3/4”
3”
12” (305mm)
10” (254mm)
TOP EDGE OF FIREPLACE
COMBUSTIBLE TRIM AND
MANTELS ALLOWED IN
SHADED AREA