Installing Support Brackets (Figure 49)
A horizontal pipe support MUST BE used for each 3 feet of horizontal 
run. The pipe supports should be placed around the  pipe and nailed 
in place to framing members. There MUST BE a 3 inch clearance 
to combustibles above flue pipe and elbows and 1 inch clearance 
on both sides and bottom of the flue pipe to combustibles on all 
horizontal pipe sections and elbows. 
Vertical runs of this vent systems must be supported every 4 feet 
above the appliance flue outlet by wall brackets attached to the 
vent pipe and secured with nails or screws to structural framing 
members.
Figure 49
Installing Firestops (Figures 50, 51, 52, and 53)
Firestops are required for safety whenever the vent system passes 
through an interior wall, an exterior wall, or a ceiling. These firestops 
act as a firebreak heat shield and as a means to insure that minimum 
clearances are maintained to the vent system.
Horizontal runs in the vent system which pass through either interior 
or exterior walls, require the use of wall firestops on both sides of 
the wall through which the vent passes.
Cut  an  appropriate  sized  hole  in  wall.  See  Figure  50.  Position 
firestop on interior side of wall for hole.
Attention: Wall firestop hole is off-set towards bottom of wall 
opening. Secure with nails or screws. Continue the vent run through 
the firestop. See Figure 50.
Figure 50
Vertical runs of this system which pass through ceilings require the 
use of ONE (1) ceiling firestop at the hole in each ceiling through 
which the vent passes.
Position a plumb bob directly over the center of the vertical vent 
component and mark the ceiling to establish the center point of the 
vent. Drill a hole or drive a nail through this center point and check 
the floor above for any obstructions such as wiring or plumbing 
runs. Reposition the appliance and vent system, if necessary, to 
accommodate ceiling joists and/or obstructions.
Cut an appropriate sized hole through the ceiling, using the center 
point  previously  marked.  See  Figure  51.  Frame  the  hole  with 
framing lumber the same size as the ceiling joists. See Figure 51
If the area above the ceiling is NOT an attic, position and secure 
the ceiling firestop on the ceiling side of the previously cut and 
framed hole. See Figure 52. If the area above the ceiling is an attic, 
position and secure the firestop on top of the previously framed 
hole. See Figure 53.
NOTE: 
Remove insulation from the framed area in the attic before 
installing the firestop and/or vent pipes.
PIPE STRAP
STUD WALL
1” MIN.
(25.4mm)
FLUE OUTLET
48”
(1219mm)
FRAMING AND FINISHING
WALL FIRESTOP
HOLE IS OFF-SET
TOWARDS BOTTOM
OF WALL OPENING.
A
B
Vent Size
A
B
6 5/8"
10"
11"
8"
10 3/8" 12 3/8"